A-20
Manual maxGUARD
2526740000/02/03.2018
Annex
| Lagged tripping characteristic 12AT
PV
PV
PV
V
$
$
$
V
Output current
13.2 A < I ≤ 18 A
18 A < I ≤ 20 A
20 A < I ≤ 24 A
24 A < I ≤ 34 A
34 A < I ≤ 48 A
I > 48 A
Tripping time
5 s
1 s
100 ms
30 ms
10 ms
5 ms
Lagged tripping characteristic 12A
T