Factory Default configuration
3.2.3 Linking a transmitter and receiver unit
Before you start, reset the transmitter unit to factory defaults (to disable encryption).
See above for instructions. You must complete the linking process in 60 seconds.
To link the transmitter and receiver units:
1. Press and hold down the SIG Pushbutton on the receiver.
2. Power on the receiver while holding down the SIG Pushbutton
3. Release the SIG Pushbutton as soon as the Receiver LEDS flash (within 5
seconds of powering the receiver).
4. The receiver will flash all LEDs for a maximum 60 seconds while it tries to link to
the transmitter.
5. Power on the transmitter. The transmitter sends a special “Link” message to the
receiver.
6. When the units link, the receiver lights all LEDs for 2 seconds before returning to
normal operation.
If the receivers LEDs are still flashing after 60 seconds, the units are not linked
and you should retry the linking process by powering the transmitter off and on
again. If you exceed the 60 seconds, you must restart the linking process from
step 1.
NOTE
7. You can now bench test your configuration before deploying.
30