background image

General Data

Transducers

=

x

Application

Transducers convert power current and voltage quantities or proccess
control inputs into proportional load independent DC current or voltage
outputs.

for measuring

AC current or AC voltage,
active or reactive power,
frequency,
phase angle (

ϕ

 ) / power factor (cos 

ϕ

 ),

DC current or DC voltage,
standard signals,
temperature

Technical Data

case details

projecting case clamping to DIN mounting rail
(to DIN EN 50 022 – 35)

material of case

ABS/PC black
self - extinguishing to UL rating 94 V–0

terminals

screw - terminals

wire cross - section

4 mm

2

 max.

enclosure code

IP 40 case
IP 20 terminals

dielectric test

3.7 kV measuring circuits and power supply
to output

class of protection

II

excess voltage 

CAT 

II

category
pollution level

2

climatic suitability

climatic class 3 acc. to VDE/VDI 3540 sheet 2

operating temperature –10 ... +55

o

C

range
storage temperature

–25 ... +65

o

C

range
relative humidity

75% annual average, non - condensing

Outputs

current output

output current

I

A

load independent DC current 0 ... 20 mA
or optionally 0 ... 10 mA, 0 ... 5 mA,
4 ... 20 mA (”live zero”), –20 ... 0 ... 20 mA
(bipolar output only with wide range supply)

load range

R

A

0 ... 10 V / I

AN

current limitation

to approx.120% of full–scale value,
other ratings on request

voltage output

output voltage

U

A

load independent DC voltage 0 ... 10 V or
optionally 2 ... 10 V (”live zero”), –10 ... 0 ... 10 V
(bipolar output only with wide range supply)

load

R

A

 4 k

W

load error

 0.1% based on 50% load change

residual ripple

 1%

rms

response time

approx.  500 ms

idling voltage

 15 V

(Ratings do not apply completely to self - powered transducers.)

Auxiliary Supply

auxiliary voltage

 U

HN

230 V AC (195 ... 253 V), 48 ... 62 Hz

optional

115 V AC (98 ... 126 V), 48 .. 62 Hz
24 V DC (20 ... 72 V)

wide range supply

20 ... 100 V DC resp. 20 ... 70 V AC
90 ... 357 V DC resp. 65 ... 253 V AC

galvanic isolation between input, output and auxiliary supply circuits

Short Form Data

Transducers for
AC Current or
AC Voltage

A1U 2.2
V1U 2.2

=

J/U

Inputs

input quantity

sinusoidal AC current or
sinusoidal AC voltage

frequency range

48 ... 62 Hz or
16

2

/

3

 Hz, 100 Hz, other ratings on request

power consumption

 0.4 VA

operating voltage

600 V max.

measuring ranges

A1U 2.2

V1U 2.2

rated current I

EN

rated voltage U

EN

in the range

0 ... 200

m

A up to 5 A 0 ... 60 mV up to 600 V

(also for use on transformer)

current input

voltage input

measuring range

0 ... I

EN

0 ... U

EN

modulation range

1.2 I

EN

1.2 U

EN

permissible

1.2 I

EN 

continuously

1.2 U

EN 

continuously

overload limit

10  I

EN

 1 s max.

2  U

EN

 1 s max.

Other Ratings

outputs

refer to 

General Data

accuracy

class 0.5

 (

±

0.5% of end value)

auxiliary voltage

refer to 

General Data

dimensions

 WxHxL

22.5 mm x 80 mm x 115 mm

weight

approx. 0.12 kg

for detailed information

refer to Data Sheet No. 061.##

prices

refer to Price Sheet No. 061.##

Summary of Contents for A1U 2.2

Page 1: ...ional Transducer MMU 3 0 for Frequency FU 2 2 for Phase Angle cos CU 2 2 for DC Current or DC Voltage AUD VUD 2 2 for RMS Current or RMS Voltage AUE VUE 2 2 for Temperature PTU 2 0 Isolation Transduce...

Page 2: ...UA load independent DC voltage 0 10 V or optionally2 10 V live zero 10 0 10 V bipolar output only with wide range supply load RA 4 kW load error 0 1 based on 50 load change residual ripple 1 rms resp...

Page 3: ...nd Reactive Power EW 2 2 EB 2 2 DGW 2 2 VGW 2 2 DUW 2 2 VUW 2 2 DGB 2 2 VGB 2 2 DUB 2 2 VUB 2 2 P Q with mP Inputs input quantity sinusoidal AC current voltage measuring unit PE active or reactive pow...

Page 4: ...os CU 2 2 with mP Inputs input quantity sinusoidal AC current voltage measuring unit phase angle power factor in E single phase AC system or D 3 phase 3 wire balanced load system measuring ranges 37 0...

Page 5: ...tional outputs additional 1 to 3 modules each module WxHxL 22 5 mm x 80 mm x 115 mm weight approx 0 6 kg basic version for detailed information refer to Data Sheet No 055 prices refer to Price Sheet N...

Page 6: ...d value class 0 2 0 2 of end value only for DC models on request auxiliary voltage refer to General Data dimensions WxHxL 22 5 mm x 80 mm x 115 mm weight approx 0 12 kg for detailed information refer...

Page 7: ...RS232 RS485 Converter AP RS232 485 RS232 RS485 Function The converter is directly plugged to a 9 contact serial interface of a PC It converts the RS232 signals of the PC into standardized RS485 signal...

Page 8: ...dependent DC current rated current IAN 4 20 mA load range RA 0 500 W based on 20 mA load error 0 1 based on 50 load change residual ripple 1 rms of IAN with load RAN idling voltage 16 V response time...

Reviews: