General Data
Transducers
=
x
Application
Transducers convert power current and voltage quantities or proccess
control inputs into proportional load independent DC current or voltage
outputs.
for measuring
AC current or AC voltage,
active or reactive power,
frequency,
phase angle (
ϕ
) / power factor (cos
ϕ
),
DC current or DC voltage,
standard signals,
temperature
Technical Data
case details
projecting case clamping to DIN mounting rail
(to DIN EN 50 022 – 35)
material of case
ABS/PC black
self - extinguishing to UL rating 94 V–0
terminals
screw - terminals
wire cross - section
4 mm
2
max.
enclosure code
IP 40 case
IP 20 terminals
dielectric test
3.7 kV measuring circuits and power supply
to output
class of protection
II
excess voltage
CAT
II
category
pollution level
2
climatic suitability
climatic class 3 acc. to VDE/VDI 3540 sheet 2
operating temperature –10 ... +55
o
C
range
storage temperature
–25 ... +65
o
C
range
relative humidity
≤
75% annual average, non - condensing
Outputs
current output
output current
I
A
load independent DC current 0 ... 20 mA
or optionally 0 ... 10 mA, 0 ... 5 mA,
4 ... 20 mA (”live zero”), –20 ... 0 ... 20 mA
(bipolar output only with wide range supply)
load range
R
A
0 ... 10 V / I
AN
current limitation
to approx.120% of full–scale value,
other ratings on request
voltage output
output voltage
U
A
load independent DC voltage 0 ... 10 V or
optionally 2 ... 10 V (”live zero”), –10 ... 0 ... 10 V
(bipolar output only with wide range supply)
load
R
A
≥
4 k
W
load error
≤
0.1% based on 50% load change
residual ripple
≤
1%
rms
response time
approx. 500 ms
idling voltage
≤
15 V
(Ratings do not apply completely to self - powered transducers.)
Auxiliary Supply
auxiliary voltage
U
HN
230 V AC (195 ... 253 V), 48 ... 62 Hz
optional
115 V AC (98 ... 126 V), 48 .. 62 Hz
24 V DC (20 ... 72 V)
wide range supply
20 ... 100 V DC resp. 20 ... 70 V AC
90 ... 357 V DC resp. 65 ... 253 V AC
galvanic isolation between input, output and auxiliary supply circuits
Short Form Data
Transducers for
AC Current or
AC Voltage
A1U 2.2
V1U 2.2
=
J/U
Inputs
input quantity
sinusoidal AC current or
sinusoidal AC voltage
frequency range
48 ... 62 Hz or
16
2
/
3
Hz, 100 Hz, other ratings on request
power consumption
≤
0.4 VA
operating voltage
600 V max.
measuring ranges
A1U 2.2
V1U 2.2
rated current I
EN
rated voltage U
EN
in the range
0 ... 200
m
A up to 5 A 0 ... 60 mV up to 600 V
(also for use on transformer)
current input
voltage input
measuring range
0 ... I
EN
0 ... U
EN
modulation range
1.2 I
EN
1.2 U
EN
permissible
1.2 I
EN
continuously
1.2 U
EN
continuously
overload limit
10 I
EN
1 s max.
2 U
EN
1 s max.
Other Ratings
outputs
refer to
General Data
accuracy
class 0.5
(
±
0.5% of end value)
auxiliary voltage
refer to
General Data
dimensions
WxHxL
22.5 mm x 80 mm x 115 mm
weight
approx. 0.12 kg
for detailed information
refer to Data Sheet No. 061.##
prices
refer to Price Sheet No. 061.##