Part Number 550-142-302/0520
CGi
SERIES 4 — GAS-FIRED WATER BOILER —
Boiler Manual
59
Troubleshooting — control module lights
(cont.)
11c
CHART 7 ––
Troubleshooting LWCO and POWER light Solid
and/or “LCO” shown on display
Electrical shock hazard
!K$Z
TURN OFF POWER
Z# @
[$# $
• System is losing water.
• Repair leak and retest.
Is boiler pressurized?
Yes
No
• System was low on water.
• Check system fill piping for
leaks or damage.
• Pressurize boiler to system design pressure.
Are lights still solid?
No
Yes
• Check system for leaks.
Is system leaking or not
maintaining pressure?
No
Yes
• LWCO sensor is bad or fouled.
• Clean LWCO sensor
• Retest.
Are lights still solid?
No
Yes
• Sensor is bad. Replace sensor.
• Retest.
• Sensor was fouled.
• Check water quality and
maintenance schedule.