Part Number
550-110-710/0107
9
GOLD CGi Gas-Fired Water Boiler — Boiler Manual
3
System or zone circulator
7
System temperature valves (see instructions to the
left for adjusting valves)
8
Blend temperature gauge
9
Relief valve
10
Automatic air vent (with diaphragm-type expan-
sion tank), or connect to tank fitting (closed-type
expansion tank).
DO NOT
use an automatic air vent
when using closed-type expansion tank. It would
allow air to leave the system, causing waterlogging
of the expansion tank.
11
Fill valve
12
Diaphragm-type or bladder-type expansion tank,
if used (For closed-type expansion tank, pipe from
top of air separator to tank fitting as in
Figure 17
,
page 1.)
Figure 24
System-bypass piping — Zoning with
zone valve or circulators, return water
130°F or higher — (Alternative to boiler-
bypass piping Figures 22 and 23)
Figure 25
Piping refrigeration systems
4e
Prevent chilled water from
entering boiler
Water piping — refrigeration system
Install boiler so that chilled medium is piped in parallel
with the heating boiler. Use appropriate valves to prevent
chilled medium from entering boiler. See Figure 18 for
typical installation of balancing valve and check valve.
If boiler is connected to heating coils located in air han-
dling units where they can be exposed to refrigerated
air, use flow control valves or other automatic means to
prevent gravity circulation during cooling cycle.
Piping — low temperature systems
(continued)
4d