2

 

2.1.2 Making a NEMA-4 Mounting 

Panel  
Details

 

The unit can be mounted into panels with a depth of 4”(105mm).    It is recommended that 
the unit be mounted on the front panel of a steel enclosure, through an appropriate opening. 
Allow a clearance of 1”(25mm) around the sides of the unit for mounting hardware. Allow 
clearance for cable connections to the back of the unit. Unit depth may vary according to 
cable type used. Typically, plan a depth to accommodate at least 4”(105mm) behind the 
panel. 

NEMA-4 
Mounting

 

Put the unit through the panel cut out. Slide the clamps into the 4 holes provided around 
the case. Tighten the clamping screws in an even pattern until the unit is secured in the 
panel. 

Caution!

 

Do not over tighten mounting clamps! 

Note:

 

Specifications 

Note: To seal to NEMA-4 specifications, all supplied mounting clamps must be used and 
panel cannot flex more than 0.010”. 

2.1.3 Environmental Considerations 

 

z

 

The MT-600/8000 are to be used indoors as built in displays. Make sure that the displays 
are installed correctly and that the operating limits are followed (See Specifications). 

z

 

Do not operate the unit in areas subject to explosion hazards due to flammable gases, 
vapors or dusts. 

z

 

The unit should not be installed where fast temperature variations and/or high humidity 
are present. This will cause condensation of water in the device. 

z

 

Do not install these terminals in environments where have inflammable gases. 

 

2.2 Power Connections 

Make sure that all local and national electrical standards are met when the installing the unit. 
Contact your local authorities to determine which codes apply. 

2.2.1 Power Requirements 

 

 

Power

 

The MT-600/8000 can be powered by DC power only. The specified 
voltage range is 

24±20%

 Volts DC. This insures compatibility with most 

controller DC systems.   

The power conditioning circuitry inside the unit is accomplished by a 
switching power supply. The peak starting current can be as high as 
700mA. 

 

Fusing 
Requirements

 

If the display does not come on within 5 seconds of power up, remove 
power. An internal fuse will prevent damage if the polarity of the DC 
power is incorrect. Check wiring to insure proper connections and try to 
power up again. 

 

Caution 
High Voltage

 

An Internal fuse will prevent damage for over voltage condition however 
it isn’t guaranteed. 

DC voltage sources should provide proper isolation from main AC power 
and similar hazards. 

 

Caution 
Emergency 
Stop

 

A Hard-wired EMERGENCY STOP should be fitted in any system using 
an MT-600/8000 to comply with ICS Safety Recommendations. 

 

Summary of Contents for MT-8070iH

Page 1: ...00 8000 Series has been tested to conform to European CE requirements This means that the circuitry is designed to resist the effects of electrical noise This does not guarantee noise immunity in severe cases Proper wire routing and grounding will insure proper operation Mechanical Environment Avoid installing units in environments where severe mechanical vibration or shocks are present 2 0 Instal...

Page 2: ...le gases vapors or dusts z The unit should not be installed where fast temperature variations and or high humidity are present This will cause condensation of water in the device z Do not install these terminals in environments where have inflammable gases 2 2 Power Connections Make sure that all local and national electrical standards are met when the installing the unit Contact your local author...

Page 3: ...e noise into a system but if necessary an earth connection should be made from the power supply return point to the central star earth point Ground conductors should be as short and as large in size as possible The conductors must always be large enough to carry the maximum short circuit current of the path being considered Ground conductors should be connected to a tree from a central star earth ...

Page 4: ...tended as safeguards against the failure of critical components and the effects of such failures or the inadvertent errors that might be introduced if programs are changed while the equipment is in operation z The ICS 3 304 81 Safety Recommendations are reproduced by permission of the National Electrical Manufacturers Association from NEMA ICS 3 304 2 3 Communications Connections The ports as you ...

Page 5: ... by the USB 2 0 client port Support USB 2 0 client interface The cable regulation must accord with HI SPEED USB Revision 2 0 SHIELDED How to install USB driver of HMI i series i Series HMI support the function of using Mini USB cable to download projects from PC It is necessary to install USB driver of HMI on PC before at the first time enjoying this function The HMI models MT6050i MT6056i MT6070i...

Page 6: ...n parameter will store at Flash Rom z If losing or forgetting system passwords users can set Dip Switch 1 to ON position the rest of Dips remain on OFF position and then reboot MT8000 series Under this situation MT8000 series will jump to Touch Adjust Touch screen calibration mode After calibration the pop up window appears as the illustration below Users will be inquired if restoring the system p...

Page 7: ...2 2005 z EN 55024 1998 A1 2001 A2 2003 3 0 Specifications MT6070iH MT8070iH MT607i Hardware Specification Display 7 TFT LCD Brightness 300 cd m2 Color 65 536 colors Contrast Ratio 500 1 Resolution WxH dots 800 x 480 Back light LED Backlight life time avg 30 000 hr min Touch panel 4 wires resistive type Touch Accuracy Active Area Length X 2 Width Y 2 I O port COM1 RS 232 RS 485 2W 4W COM2 RS232 COM...

Page 8: ...g current leakage from machine platform and incorrect input power c If the product has been maintained in a manner not conforming to product s instructions or has been modified in any way d If the serial number has been defaced or removed 4 0 Dimensions of MT 607i MT 6070iH MT 8070iH Cutout dimensions 192mm 7 559 W x 138mm 5 433 H Front View Rear View Bottom View a DIP SW Reset button g Com1 RS485...

Reviews: