3

 

 

Caution 
Supply Voltage 
Condition 

Do not power the MT-600/8000 and inductive DC loads, or input 
circuitry to the controller, with the same power supply. Note: The 24 
VDC output from some controllers may not have enough current to 
power the MT-600/8000. 

 

Caution   
Wire Routing 

Wire lengths should be minimized (Maximum 1600’ (500 m) shielded, 
1000’ (300 m) unshielded). 
Wires should be run in pairs with a neutral or common paired with a hot 
or signal line. 
If wiring is to be exposed to lightning or surges, use appropriate surge 
suppression devices. 
Keep AC, high energy, and rapidly switching DC wiring separate from 
signal wires. 
Equip ungrounded DC supplies with a resistor and capacitor in parallel 
to earth ground. This provides a path for static and high frequency 
dissipation. Typical values to use are 1MOhm and 4700pF. 

 

Caution ! 
 

To prevent the HMI from becoming damaged or having sound output 
issues, after turning the device off, please wait 10 seconds before 
turning the device on again. 

 

Connection 

 

To make a connection, strip about 3/8” of insulation off the end of the 
wire, turn the connector screw counterclockwise until the gap is wide 
open, insert the wire all the way in, and turn the screw clockwise until 
it’s tight. 

Connect positive DC line to the ‘+24V’ terminal and the DC ground to 
the ‘0V‘ terminal. 

2.2.2 Grounding Requirements 

 

 

Chassis ground must be used.    DC ground is not directly coupled to Earth 
ground internally. It is preferable not to ground DC negative return to chassis 
ground as poor site earths can introduce noise into a system, but if necessary 
an earth connection should be made, from the power supply return point to 
the central star earth point. Ground conductors should be as short and as large 
in size as possible. The conductors must always be large enough to carry the 
maximum short circuit current of the path being considered. Ground 
conductors should be connected to a tree from a central star earth ground 
point. This ensures that no ground conductor carries current from any other 
branch. 

2.2.3 CE Requirements 

To make an MT-600/8000 comply with EMC directives, and to reduce susceptibility to electrical 

interference, a separate #14 AWG ground wire should be taken to the chassis ground terminal of the 
power connector. This ground connection should be run directly to the central star earth connection 
point (as recommended in most Installation Instructions). 

2.2.4 Safety Guidelines 

This section presents recommended installation practices, and procedures. Since no two 

applications are identical, these recommendations should be considered as guidelines. 

 

Hardware 
Considerations 

WARNING! 

The system designer should be aware that devices in Controller systems could 
fail and thereby create an unsafe condition. Furthermore, electrical 
interference in an operator interface, such as an MT-600/8000, can lead to 
equipment start-up, which could result in property damage and/or physical 
injury to the equipment operator. 

If you, or your company, use any programmable control systems that require 
an operator or attendant, you should be aware that this potential safety hazard 
exists and take appropriate precautions. Although the specific design steps 
depend on your particular application, the following precautions generally 
apply to installation of solid-state programmable control devices. In addition, 

Summary of Contents for MT-8150X

Page 1: ...0 Series has been tested to conform to European CE requirements This means that the circuitry is designed to resist the effects of electrical noise This does not guarantee noise immunity in severe cases Proper wire routing and grounding will insure proper operation Mechanical Environment Avoid installing units in environments where severe mechanical vibration or shocks are present 2 0 Installation...

Page 2: ...hat the operating limits are followed See Specifications Do not operate the unit in areas subject to explosion hazards due to flammable gases vapors or dusts The unit should not be installed where fast temperature variations and or high humidity are present This will cause condensation of water in the device Do not install these terminals in environments where have inflammable gases 2 2 Power Conn...

Page 3: ...an earth connection should be made from the power supply return point to the central star earth point Ground conductors should be as short and as large in size as possible The conductors must always be large enough to carry the maximum short circuit current of the path being considered Ground conductors should be connected to a tree from a central star earth ground point This ensures that no groun...

Page 4: ... programs are changed while the equipment is in operation The ICS 3 304 81 Safety Recommendations are reproduced by permission of the National Electrical Manufacturers Association from NEMA ICS 3 304 2 3 Communications Connections The ports as you look at the back of the case are the ports for connecting to a PLC or some external device Controller Connectors 2 3 1 Connector COM1 RS232 COM2 RS232 C...

Page 5: ...e Com1 RS232 RS485 2wire 4wire Com3 RS232 RS485 mode can be set by CECP In the Windows CE desktop 2 3 3 USB Host port USB 2 0 Host interface supports USB mouse keyboard USB Flash Drive and printer While using external hard drive please use external power supply Do not use USB port to charge external device 2 3 4 Connecter Wire MT8 Ethernet RZC045120 Direct connect Ethernet crossover cable MT8000 E...

Page 6: ...MT 600 8000 Series EMC Directive 2004 108 EC electromagnetic emissions and immunity UL508 ISBN 0 7629 0404 6 machine safety for use in Pollution Degree 2 Environment MT600 products will be CE marked to indicate compliance with the EMC Directive The MT 600 8000 Series has been designed to operate satisfactorily in electromagnetic noise immunity and without emitting high levels of electrical noise i...

Page 7: ...t Support SD SDHC RTC Built in CR2032 3V lithium battery General Specification Input Power 24 10 VDC 21 6 26 4VDC Power Isolator Inside Power Consumption 1 6 A 24VDC Isolated Power Supply Built in CE FCC Complies with EN 55022 1998 A1 2000 A2 2003 Class A EN 61000 3 2 2000 A2 2005 EN 61000 3 3 1995 A1 2001 EN 55024 1998 A1 2001 A2 2003 Voltage resistance 500VAC 1 min Isolation resistance Exceed 50...

Page 8: ...M3 RS485 COM3 RS232 COM1 RS232 COM2 RS232 m j VIP1 VIP2 a IDE interface DOM slot i USB Host port x 2 b Mini USB j Ethernet port 10 100 Base T c Fuse k Com1 RS485 Com3 RS485 Com3 RS232 d Power connector l Com1 RS232 Com2 RS232 e Reset button m SD CARD SLOT f VESA 75mm screw holes n Video Input Port x 2 V2 Only g Mic In h Line Out Cutout Dimensions MT615X MT8150X 352mm 13 86 Wx279mm 10 98 H GME8615V...

Reviews: