© 2022 WEINZIERL ENGINEERING GmbH
Seite 5/22
Summary of the states of the LEDs 1
– 4
❺
:
2.2.2 Manual operation RF
Briefly pressing button B
❼
activates manual operation for mode RF.
Pressing button A
❻
briefly deactivates/activates the forwarding of the group telegrams. This is
indicated by LEDs 5 and 6
❺
.
Pressing button B
❼
briefly deactivates/activates the forwarding of the physically addressed
telegrams, the broadcast telegrams and the system broadcast telegrams. This is indicated by
LEDs 7 and 8
❺
.
Pressing button A
❻
or button B
❼
for a long time exits manual operation.
Manual operation can be locked in the ETS database.
Summary of the states of the LEDs 5
– 8
❺
:
LED Status
Meaning
LEDs 1 and 2 light green
Manual operation is active.
Forwarding of group telegrams via KNX TP is active.
LEDs 1 and 2 off
Manual operation is active.
Forwarding of group telegrams via KNX TP is not active.
LEDs 3 and 4 light green
Manual operation is active.
Forwarding of physically addressed telegrams and
broadcast telegrams via KNX TP is active.
LEDs 3 and 4 off
Manual operation is active.
Forwarding of physically addressed telegrams and
broadcast telegrams via KNX TP is not active.
LED Status
Meaning
LEDs 5 and 6 light green
Manual operation is active.
Forwarding of group telegrams via KNX RF is active.
LEDs 5 and 6 off
Manual operation is active.
Forwarding of group telegrams via KNX RF is not active.
LEDs 7 and 8 light green
Manual operation is active.
Forwarding of physically addressed telegrams, broadcast telegrams and
system broadcast telegrams via KNX RF is active.
LEDs 7 and 8 off
Manual operation is active.
Forwarding of physically addressed telegrams, broadcast telegrams and
system broadcast telegrams via KNX RF is not active.