KNX ENO 634 

WEINZIERL ENGINEERING GmbH 

EN 

2013-08-14 

Page 7/11 

 

Fig. 15: Room operation panel 

 
Various  room  controls  with  temperature,  presence, 
and  day  /  night  switches  can  be  a  linked.  Depending 
on  the  type,  setpoint  values,  temperature  limits  and 
multiple fan speeds can be set. 
 

Comm.-Object 

Type KNX 

Size 

Channel…: Fan speed 

5.001 

1 Byte 

Channel…: Temp. setpoint 

9.001 

2 Byte 

Channel…: Humidity 

9.007 

2 Byte 

Channel…: Temperature 

9.001 

2 Byte 

Channel…: Occupancy 

1.018 

1 Bit 

Channel…: Night 

1.001 

1 Bit 

Channel…: Automatic Fan 

1.001 

1 Bit 

 

Automated meter reading 

 

Abb. 16: Automated meter reading 

 
Each  channel  can  read  up  to three  meters.  For  each 
counter,  there  are  two  communication  objects  of  4 
bytes  available:  One  value  for  the  current  consump-
tion and one value for the total consumption. 
 

Comm.-Object 

Type KNX 

Size 

Channel…: Count 

12.001 

4 Byte 

Channel…: Count rate [1/s] 

12.001 

4 Byte 

Channel…: Total energy [kWh] 

13.013 

4 Byte 

Channel…: Current Energy [W] 

9.024 

2 Byte 

Channel…: Total gas [m³] 

14.076 

4 Byte 

Channel…: Current Gas [l/h] 

9.025 

2 Byte 

Channel…: Total water [m³] 

14.076 

4 Byte 

Channel…: Current water [l/h] 

9.025 

2 Byte 

 
 

Environmental and weather sensors 

 

Fig.17: Environmental sensors 

 
The following environmental sensor types can be pro-
grammed:  Weather  station,  sunlight  (northern  hemi-
sphere), date, time and day, direction and geographic 
position. Depending on the setting, there are different 
communication objects for each sensor type. 
 
 
Weather station: 

Comm.-Object 

Type KNX 

Size 

Channel…: Dawn 

9.004 

2 Byte 

Channel…: Temperature 

9.001 

2 Byte 

Channel…: Wind speed 

9.005 

2 Byte 

Channel…: Night 

1.001 

1 Bit 

Channel…: Rain 

1.001 

1 Bit 

 
Sun intensity, northern hemisphere: 

Comm.-Object 

Type KNX 

Size 

Channel…: Sun west 

9.004 

2 Byte 

Channel…: Sun south 

9.004 

2 Byte 

Channel…: Sun east 

9.004 

2 Byte 

 
Date: 

Comm.-Object 

Type KNX 

Size 

Channel…: Date 

11.001 

3 Byte 

 
Time and Day: 

Comm.-Object 

Type KNX 

Size 

Channel…: Time 

10.001 

3 Byte 

 
Direction: 

Comm.-Object 

Type KNX 

Size 

Channel…: Elevation 

8.011 

2 Byte 

Channel…: Azimuth 

8.011 

2 Byte 

 
Geographic position: 

Comm.-Object 

Type KNX 

Size 

Channel…: degree of longitude 

14.007 

4 Byte 

Channel…: degree of latitude 

14.007 

4 Byte 

 
 

Digital input 

 

Fig. 18: Digital input 

 

It  supports  digital  inputs  with  and  without  battery 
monitor.  The  digital  inputs  with  battery  monitor  send 
an additional telegram when the battery is weak. 
 

Summary of Contents for KNX ENO 634

Page 1: ... gateway supports logical and control functions and in cludes radio repeater functionality The KNX ENO 634 is divided in 32 channels Each channel can be as signed to one of the following functions Link from EnOcean sensor to KNX Switch functions Switching Dimming Shutter Scene Window handles Window contacts Access card switches Press switches Temperature sensors Humidity sensors Light sensors Pres...

Page 2: ...er Deleting links for RF sensors and Deleting links for RF actua tors Key press T1 short Exit Leave channel linking mode Key press T2 long Add Start linking mode Refer to chapter Linking mode for sensors and Linking mode for actuators Key press T2 short Active Activate or change the channels 1 32 Key press T3 Activate KNX Prog mode The KNX device can now receive a new individual ad dress Refer to ...

Page 3: ...handles RPS after 3 tel must be selected The sensor has to send three telegrams within 10 se conds to be linked The link mode is terminated by a short press of the left key T1 as well as automatically after 5 minutes without operation Quick guide linking mode for RF sensors 1 T2 short press to select the desired channel 2 T2 long press to activate the learning mode Wait for ENO 3 Activate the lear...

Page 4: ...n telegram will be compared to see if it has been assigned to a Channel If so the channel is shown shortly in a matrix on the LCD display De pending on the configured function there will be one or more telegrams sent on the bus The gateway only sends telegrams to the KNX bus when a correspond ing EnOcean telegram has been received If an EnOcean telegram is not assigned to any channel only the sign...

Page 5: ...ush if the actu ator supports this Comm Object Type KNX Size Channel Scene 18 001 1 Biyte Other switches and contacts Fig 8 Other switches and contacts In the submenu Other switches and contacts window contacts window handles key card switches and pressure switches can be integrated For window handle sensors three states can be de tected Window is open tilted or closed When turn ing the handle in ...

Page 6: ...is available as a 2 byte float value Comm Object Type KNX Size Channel Lux 9 004 2 Byte Presence sensors Fig 12 Occupancy sensors In this section presence sensors and motion detectors can be integrated Comm Object Type KNX Size Channel presence 1 018 1 Bit Light Temperature und occupancy sen sors Fig 13 Light Temperature und occupancy sensors Light intensity and temperature are each mapped to a co...

Page 7: ...076 4 Byte Channel Current water l h 9 025 2 Byte Environmental and weather sensors Fig 17 Environmental sensors The following environmental sensor types can be pro grammed Weather station sunlight northern hemi sphere date time and day direction and geographic position Depending on the setting there are different communication objects for each sensor type Weather station Comm Object Type KNX Size...

Page 8: ...le contact input On or off will be sent Comm Object Type KNX Size Channel Window open 1 019 1 Byte HVAC Actuator for valve drive Fig 21 HVAC actuator In this configuration battery operated heating and air actuators can be controlled The temperature values sent by the actuator will be sent to the bus A tele gram is sent when the EnOcean device signals a low battery Battery operated heating and vent...

Page 9: ...automatic control A typical application for the fully automatic control is the lighting of a corridor The light is turned on in presence when the current brightness value is below the threshold By manual operation the light can be switched on or off for a specific time Semi automatic control The semiautomatic mode allows the user or residents to turn the lights on and off manually The semi automat...

Page 10: ...r level corresponding to the config ured condition Is this condition is fulfilled the value 1 will be sent via the output datapoint Comm Object Type KNX Size Channel Trigger value in A D 5 000 1 Byte Channel Trigger binary out A D 1 001 1 Bit Trigger float Up to 2 float triggers can be implemented on one channel The trigger compares the input value with the configured trigger level corresponding t...

Page 11: ...d data is displayed also in hexadecimal cod ing in the second numeric part If a message is sent by the gateway it is displayed in the first position of the line with an S The ID used by the gateway and the transferred data are also shown Fig 27 EnOcean bus monitor KNX bus monitor The KNX bus monitor displays the messages at the object level Therefore only group telegrams are visi ble which address...

Reviews: