background image

 

©

2017 WEINZIERL ENGINEERING GmbH 

Page 2/8

 

 

KNX IP LineMaster 762 as area and line coupler 

 

The KNX IP LineMaster 762 has a filter table and thus contrib-
utes to reducing the bus load. The filter table (8kB) supports the 
extended group address range and is automatically generated 
by the ETS. 

Because of the speed difference between the Ethernet (100 
Mbit/s) and KNX TP (9.6 kbit/s), a far greater number of tele-
grams can be transmitted on IP. If several consecutive telegrams 
are transmitted for the same line, they must be buffered in the 
router to avoid telegram loss. The KNX IP LineMaster 762 has a 
memory for 150 telegrams (from IP to KNX). 

 

Bus access function (KNXnet/IP Tunneling) 

The KNX IP LineMaster 762 can be used as an interface to KNX. 
The KNX bus can be accessed from any point in the LAN. The 
device supports up to 6 simultanous Tunneling connections. For 
each connection an additional individual address must be as-
signed. This is described in the following sections. 

 

Installation and Connection 

The KNX IP LineMaster 762 is designed for installation on DIN 
rail with a width of 6 units (108 mm). It features the following con-

trols (

❼❽❾

) and displays (

): 

 

 

Settings 

The settings  of the device can be accessed via  

1. 

Local display on the device (partly) 

2. 

ETS (Version 4.2 or higher)

 

 

 

The KNX Programming Mode is activated/deactivated by 
simultaneously pressing the buttons 

❽❿

 

– when acti-

vated the programming LED 

 

lights up. 

 

Programming and status LED 

 

The red LED on the front panel is used to display the KNX pro-
gramming mode and errors. The LED can have the following 
states: 

 

LED off: The programming mode is not active and 
there is no error (normal operating mode). 

 

LED lights up: The programming mode is active, 
any errors are not visualized/notified by the LED, 
but can be read on the display. 

 

LED flashes quickly: The programming mode is 
not active. The rapid flashing indicates one of the 
following faults: 

o

 

Overload (sum of the current of auxiliary 
and Bus power) 

o

 

The device is not loaded correctly, for 
example, a cancelled download. 

Factory default settings 

The following configuration is set by factory default: 

Individual device address: 

 

 

15.15.0 

Number of configured KNXnet/IP tunneling con.:  6 
Individual address of tunneling con. 1:   

15.15.240 

Individual address of tunneling con. 2:   

15.15.241 

Individual address of tunneling con. 3:   

15.15.242 

Individual address of tunneling con. 4:   

15.15.243 

Individual address of tunneling con. 5:   

15.15.244 

Individual address of tunneling con. 6:   

15.15.245 

IP address assignment: 

 

 

DHCP 

 

Direct Setting via display on device 

A.  Startup and idle display 

During startup of the device, the physical 
address and the status of the application 
is displayed. 
The device name “KNX IP LineMaster” 
can be changed within ETS parameter 
settings. 

 

The status can be one of the following values: 

 

Running:

 Application is loaded and running 

 

Stopped:

 The application is stopped -

 

LED for 

Programming Mode is flashing 

 

Unloaded: 

The application is not loaded- 

 

LED 

for Programming Mode is flashing 

 

Loading:

 The application is currently loading by 

ETS 

 

Overload:

 The output current is above the limit of 

900mA - 

 

LED for Programming Mode is flash-

ing 

 

Manual:

 Parameterized coupler settings were 

manually overwritten (filter, repetition and 
acknowledge) via the manual operation in the de-
vice display. By pressing long on on Enter 

, the 

normal operating mode, as parameterized, is re-
stored. 

The power supply functionality (KNX and auxiliary voltage) is 
not dependent whether the application is running or not. 

After 10 minutes of inactivity the display will turn into 
screensaver mode (blank screen with a bouncing dot) to 
safe display life time. Press any key to turn the display 
on again. 

Switch

LAN

KNX IP
LineMaster 762

1.0.0

KNX

1.1.0

1.2.0

1.2.1

1.2.6

1.2.5

1.2.4

1.2.3

1.2.2

1.1.1

1.1.6

1.1.5

1.1.4

1.1.3

1.1.2

KNX IP
LineMaster 762

2.1.0

KNX

2.1.1

2.1.6

2.1.5

2.1.4

2.1.3

2.1.2

2.1.7

2.1.12

2.1.11

2.1.10

2.1.9

2.1.8

 

 

 

Aux. Power Out 30 V DC 

 

KNX Bus Out 

 

Power In 230 V AC 

 LAN Connector 

 OLED Display 

 LED for Prog. Mode 

 Up Button 

 Down Button 

 Escape Button 

 Enter Button 

 

 

Summary of Contents for KNX IP LineMaster 762

Page 1: ...coupl IP coupling of lines IP line coupler Area Backbone TP IP IP Coupling KNX Line Coupler max 15 Pcs KNX IP Router max 15 Pcs Directly via LAN Switch Main line TP TP IP Coupling KNX Line Coupler max 15x15 Pcs KNX Line Coupler max 15x15 Pcs KNX IP Router max 225 Pcs Line TP TP TP KNX IP LineMaster 762 as line coupler The individual address assigned to the KNX IP LineMaster 762 determines whether ...

Page 2: ...t of auxiliary and Bus power o The device is not loaded correctly for example a cancelled download Factory default settings The following configuration is set by factory default Individual device address 15 15 0 Number of configured KNXnet IP tunneling con 6 Individual address of tunneling con 1 15 15 240 Individual address of tunneling con 2 15 15 241 Individual address of tunneling con 3 15 15 2...

Page 3: ...owledge only when forwarding ACK acknowledge al ways NACK negative acknowledgment When answering with NACK access to the device via KNX TP is no longer pos sible see ETS parameter settings These settings are temporary Settings differing from parameterization are marked with an angular bracket The parameterized setting can be restored with a long press on Enter H Tel Counter This submenu contains t...

Page 4: ...ase section for more information As factory default the assignment of the IP address is set to au tomatically via DHCP no further IP settings are necessary To use this feature a DHCP server on the LAN must be present e g many DSL routers have an integrated DHCP server After connecting the KNX IP LineMaster 762 to the LAN it should automatically appear in the ETS within the menu Bus under Discovere...

Page 5: ...of the device Within the IP overview the IP network specific options of the KNX IP LineMaster can be changed By changing obtain an IP address automatically via DHCP to Use a static IP address static IP address the IP address sub net mask and default gateway can be set freely All changes in the properties menu become effective only after a successful application download IP address Here the IP addr...

Page 6: ...eration on device bypass filtering The duration of the manual operating mode is set here The filter table can be bypassed temporarily for commissioning or test pur poses This can be set under the menu item Filter After termi nation the normal operating mode as programmed by ETS is au tomatically processed again Routing KNX TP IP Group telegrams main group 0 to 13 Main group 0 to 13 is the standard...

Page 7: ...vidually addressed telegrams Block No individually addressed telegrams are routed to KNX TP Route All individually addressed telegrams are routed to KNX TP Filter The individual address is used to check whether the received individually addressed telegram should be routed to KNX TP Broadcast telegrams Block No received broadcast telegrams are routed to KNX TP Route All received broadcast telegrams...

Page 8: ...se direct IP connection if available in the ETS menu Bus Connections Options The download is then directly performed in the device and is not visi ble in the ETS group monitor Due to the significantly shorter transmission times it is recommended to perform downloads via IP Weinzierl Engineering GmbH D 84508 Burgkirchen Alz Germany http www weinzierl de info weinzierl de WARNING The device must be ...

Reviews: