background image

 

©

2017 WEINZIERL ENGINEERING GmbH 

Page 3/8

 

 

B.  Main Menu  

By pressing 

 (arrow down) you enter 

the main menu of the device. By press-
ing 

 (enter) you enter the submenus. 

Within the menus you can use 

 (arrow 

up) and 

 (arrow down) for navigation; 

❿ 

(enter) is for confirmation and 

 

(escape) is to cancel / go back / one 
level higher. 

Router <-> Powersupply <-> System Info <-> Dev Reset <-> 
Contrast 
 

C.  Submenu Router 

The Router menu item offers the following submenus: 
IP Config <-> IP Tunnel <-> Filter <-> Rep / ACK <-> Tel 
Counter <-> Bus Errors 

 

D.  Submenu IP Config 

Select DHCP or Manual for IP configura-
tion. Within Manual you can set the IP, 
subnet and gateway. Use 

 and 

 to 

navigate/set and 

 to select. 

 

 

E.  Submenu IP Tunnel 

The KNX IP LineMaster 762 supports 6 
simultaneous KNXnet/IP tunneling con-
nections. You can display them in the 
submenu IP Tunnel including their actual 
status as well as the corresponding indi-
vidual address. 

F.  Submenu Filter 

For commissioning or test purposes, 
the filter settings parameterized by the 
ETS can be bypassed temporarily. The 
settings for broadcast telegrams (BC), 
individually addressed telegrams (IA) 
and group telegrams (main groups 0 to 
13 GA

0

 and main groups 14 to 31 GA

14

can be changed separately. The left-
hand side relates to the forwarding from 
the main (IP) to the subline (TP), the 
right-hand side to the forwarding from 
the sub (TP) to the main line (IP). The 
following options are available: - For-
ward, x Block and \ Filter. 
Settings differing from parameterization 
are marked with an angular bracket. 
The parameterized setting can be re-
stored with a long press on Enter 

 

G.  Submenu Rep / ACK 

In this submenu, the settings for repeat-
ing telegrams on the subline (TP) can be 
changed. The settings for broadcast tel-
egrams (BC), individually addressed tel-
egrams (IA) and group telegrams (GA) 
can be changed separately: --- no repeti-
tion, REP up to 3 repetitions. 

In addition, the settings for the telegram 
acknowledge can be changed on the 
subline (TP): 

ROUT

 Acknowledge only 

when forwarding, 

ACK

 acknowledge al-

ways, 

NACK

 negative acknowledgment. 

When answering with NACK, access to 
the device via KNX TP is no longer pos-
sible, see ETS parameter settings. 

These settings are temporary. 

Settings differing from parameterization 
are marked with an angular bracket. The 
parameterized setting can be restored 
with a long press on Enter 

H.  Tel Counter 

This submenu contains telegram coun-
ters. The number of forwarded telegrams 
is displayed here, separated from the di-
rection (mainline IP to subline TP and 
vice versa) and telegram type (individu-
ally addressed telegrams IA and group 
telegrams GA). The counters can be re-
seted here. 

I. 

Submenu Bus Errors 

In this submenu, you can display 

bus er-

rors

 and reset the bus error counters by 

pressing 

❿ 

(enter). 

 

 

The following errors are counted: 

 

Send errors:

 Send failed after final repetition due to 

missing ACK, NACK or BUSY. 

 

Receive errors:

 Malformed telegrams or telegram 

fragments received. 

 

Repetitions:

 Number of received repeated tele-

grams. Also own repetitions are counted. 

 

J.  Submenu Submenu Powersupply 

The Powersupply menu item offers the following submenus: 

Diagnosis <-> History <-> Bus Reset <-> Event Counters 

K.  Submenu Diagnosis 

This submenu shows actual values of 

busload

 (%), 

voltage

 (V), 

current

 (mA), 

and 

temperature

 (°C). 

The busload is an indication of number 
of telegrams in a time span. 

A value of 100 % busload is achieved by about 50 telegrams 
per second (Group Value Write, 1 Byte data). Voltage is the 
bus voltage, current the sum of bus and auxiliary current. 
The temperature is measured within the device. 

 

L.  Submenu History 

History displays the value range (min 
and max) for

 busload, voltage, current

 

and 

temperature

 over the last 24 hours. 

 

By pressing the 

 (arrow down) several 

times a graphical 

‘realtime' visualization 

is displayed: for busload, voltage, cur-
rent, and temperature. To go back to the 
main menu, press 

 (escape). 

The time span of each graph is approxi-
mately 2 minutes. 
 

M.  Submenu Bus Reset 

This submenu allows you to reset the 
KNX Bus line. Press 

❿ 

(enter) to switch 

off the KNX voltage. The default reset 
time is 30 seconds. To stop the count-
down, press 

 (escape) 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for KNX IP LineMaster 762

Page 1: ...coupl IP coupling of lines IP line coupler Area Backbone TP IP IP Coupling KNX Line Coupler max 15 Pcs KNX IP Router max 15 Pcs Directly via LAN Switch Main line TP TP IP Coupling KNX Line Coupler max 15x15 Pcs KNX Line Coupler max 15x15 Pcs KNX IP Router max 225 Pcs Line TP TP TP KNX IP LineMaster 762 as line coupler The individual address assigned to the KNX IP LineMaster 762 determines whether ...

Page 2: ...t of auxiliary and Bus power o The device is not loaded correctly for example a cancelled download Factory default settings The following configuration is set by factory default Individual device address 15 15 0 Number of configured KNXnet IP tunneling con 6 Individual address of tunneling con 1 15 15 240 Individual address of tunneling con 2 15 15 241 Individual address of tunneling con 3 15 15 2...

Page 3: ...owledge only when forwarding ACK acknowledge al ways NACK negative acknowledgment When answering with NACK access to the device via KNX TP is no longer pos sible see ETS parameter settings These settings are temporary Settings differing from parameterization are marked with an angular bracket The parameterized setting can be restored with a long press on Enter H Tel Counter This submenu contains t...

Page 4: ...ase section for more information As factory default the assignment of the IP address is set to au tomatically via DHCP no further IP settings are necessary To use this feature a DHCP server on the LAN must be present e g many DSL routers have an integrated DHCP server After connecting the KNX IP LineMaster 762 to the LAN it should automatically appear in the ETS within the menu Bus under Discovere...

Page 5: ...of the device Within the IP overview the IP network specific options of the KNX IP LineMaster can be changed By changing obtain an IP address automatically via DHCP to Use a static IP address static IP address the IP address sub net mask and default gateway can be set freely All changes in the properties menu become effective only after a successful application download IP address Here the IP addr...

Page 6: ...eration on device bypass filtering The duration of the manual operating mode is set here The filter table can be bypassed temporarily for commissioning or test pur poses This can be set under the menu item Filter After termi nation the normal operating mode as programmed by ETS is au tomatically processed again Routing KNX TP IP Group telegrams main group 0 to 13 Main group 0 to 13 is the standard...

Page 7: ...vidually addressed telegrams Block No individually addressed telegrams are routed to KNX TP Route All individually addressed telegrams are routed to KNX TP Filter The individual address is used to check whether the received individually addressed telegram should be routed to KNX TP Broadcast telegrams Block No received broadcast telegrams are routed to KNX TP Route All received broadcast telegrams...

Page 8: ...se direct IP connection if available in the ETS menu Bus Connections Options The download is then directly performed in the device and is not visi ble in the ETS group monitor Due to the significantly shorter transmission times it is recommended to perform downloads via IP Weinzierl Engineering GmbH D 84508 Burgkirchen Alz Germany http www weinzierl de info weinzierl de WARNING The device must be ...

Reviews: