N.  Submenu Event Counter 

The operating status is logged automatically in the device 
and can be viewed in this sub menu. All times as displayed 
in the format “hours:minutes”. 

Operation time: 

Summed up the com-

plete operation time of the device.

 

Run time: 

Time since the last device re-

boot. Timer starts new when device is 
powered on.

 

Restarts: 

Number of restarts. Counter 

counts up when device is powered on. 

Time > 75 °C:

 Summed up operation 

time with in-device temperature above 
75 °C.

 

Time > 640 mA:

 Summed up operation 

time with current load over 640 mA; cur-
rent load of both outputs is logged. 

Time > 900 mA:

 Summed up operation 

time with current load over 900 mA; cur-
rent load of both outputs is logged. 

To extend the lifespan of the internal memory the 

counter writes the log with a dynamic time 
span of up to 8 hours. Thus the log data may 
be lower if the device power was cut during  
a log period. 
 

O.  Submenu System Info 

This submenu displays 

information 

about the device

: serial number 

(SerNo), Application-ID (Info), App sta-
tus (State),Firmware Revision (Vers.) 
and MAC address (MAC). 

 

P.  Submenu Device Reset 

This submenu allows you to restart the 
device or to 

reset to factory settings

 

(master reset). Select one option and 
keep 

 pressed until the small anima-

tion is finished and the option is exe-
cuted. 

 

Master reset will make a new ETS application download 
necessary. 

 
Q.  Submenu Contrast 

To set the contrast of the display, select 
this entry in the menu. By pressing 

❿ 

(enter) several times you can set the 
contrast to different levels.

 

 

 

Interface settings with ETS 

Within the ETS Software KNX interfaces can be selected and set 
up via the ETS menu "Bus Interfaces".  

The ETS can access configured KNX IP LineMaster 762 even 
without a database entry. If the setup of the KNX IP LineMaster 
762 does not comply with the conditions of the KNX installation it 
must be configured via an ETS project. See the ETS database 
section for more information.  

As factory default the assign

ment of the IP address is set to “au-

tomatically via DHCP” no further IP settings are necessary. To 
use this feature a DHCP server on the LAN must be present 
(e.g. many DSL routers have an integrated DHCP server). 

After connecting the KNX IP LineMaster 762 to the LAN, it 
should automatically appear in the ETS within the menu "Bus" 
under "Discovered interfaces". 

By clicking on the discovered interface it is selected as the cur-
rent interface. On the right side of the ETS window all specific in-
formation and options of the connection appear. 

The indicated device name and the "Host Individual Address" (in-
dividual address of the device) can be changed within your ETS 
project then. 

Like all programmable KNX devices the KNX IP LineMaster 762 
has an individual address (device address) which can be used to 
access the device. It is used, for example, by the ETS when 
downloading the application to the KNX IP LineMaster 762 via 
the bus. 

For the interface function the device contains additional individ-
ual addresses that can be set in the ETS (ETS 4.2 or higher). 
When a client (e.g. ETS) sends via the KNX IP LineMaster 762 
telegrams to the bus, they contain a sender address as one from 
the additional addresses. Each address is associated with a con-
nection. Thus response telegrams can be clearly transmitted to 
the respective client. 

The additional individual addresses must be selected from the 
address range of the bus line  which the KNX IP LineMaster 762 
provides and may not be used by another device. 

Example: 

Device address 

1.1.0 

(address within ETS topology) 

Connection 1 

1.1.240  (1. additional address) 

Connection 2 

1.1.241  (2. additional address) 

Connection 3 

1.1.242  (3. additional address) 

Connection 4 

1.1.243  (4. additional address) 

Connection 5 

1.1.244  (5. additional address)  

Connection 6 

1.1.245  (6. additional address) 

The section “Individual Address” enables you to change the indi-
vidual KNX address of the currently used KNXnet/IP Tunneling 
connection. To check if the address you want to assign is unique 
within your KNX 

installation you can click the button “Address 

free?” 

 

 

 

 

 

 

 

Summary of Contents for KNX IP LineMaster 762

Page 1: ...coupl IP coupling of lines IP line coupler Area Backbone TP IP IP Coupling KNX Line Coupler max 15 Pcs KNX IP Router max 15 Pcs Directly via LAN Switch Main line TP TP IP Coupling KNX Line Coupler max 15x15 Pcs KNX Line Coupler max 15x15 Pcs KNX IP Router max 225 Pcs Line TP TP TP KNX IP LineMaster 762 as line coupler The individual address assigned to the KNX IP LineMaster 762 determines whether ...

Page 2: ...t of auxiliary and Bus power o The device is not loaded correctly for example a cancelled download Factory default settings The following configuration is set by factory default Individual device address 15 15 0 Number of configured KNXnet IP tunneling con 6 Individual address of tunneling con 1 15 15 240 Individual address of tunneling con 2 15 15 241 Individual address of tunneling con 3 15 15 2...

Page 3: ...owledge only when forwarding ACK acknowledge al ways NACK negative acknowledgment When answering with NACK access to the device via KNX TP is no longer pos sible see ETS parameter settings These settings are temporary Settings differing from parameterization are marked with an angular bracket The parameterized setting can be restored with a long press on Enter H Tel Counter This submenu contains t...

Page 4: ...ase section for more information As factory default the assignment of the IP address is set to au tomatically via DHCP no further IP settings are necessary To use this feature a DHCP server on the LAN must be present e g many DSL routers have an integrated DHCP server After connecting the KNX IP LineMaster 762 to the LAN it should automatically appear in the ETS within the menu Bus under Discovere...

Page 5: ...of the device Within the IP overview the IP network specific options of the KNX IP LineMaster can be changed By changing obtain an IP address automatically via DHCP to Use a static IP address static IP address the IP address sub net mask and default gateway can be set freely All changes in the properties menu become effective only after a successful application download IP address Here the IP addr...

Page 6: ...eration on device bypass filtering The duration of the manual operating mode is set here The filter table can be bypassed temporarily for commissioning or test pur poses This can be set under the menu item Filter After termi nation the normal operating mode as programmed by ETS is au tomatically processed again Routing KNX TP IP Group telegrams main group 0 to 13 Main group 0 to 13 is the standard...

Page 7: ...vidually addressed telegrams Block No individually addressed telegrams are routed to KNX TP Route All individually addressed telegrams are routed to KNX TP Filter The individual address is used to check whether the received individually addressed telegram should be routed to KNX TP Broadcast telegrams Block No received broadcast telegrams are routed to KNX TP Route All received broadcast telegrams...

Page 8: ...se direct IP connection if available in the ETS menu Bus Connections Options The download is then directly performed in the device and is not visi ble in the ETS group monitor Due to the significantly shorter transmission times it is recommended to perform downloads via IP Weinzierl Engineering GmbH D 84508 Burgkirchen Alz Germany http www weinzierl de info weinzierl de WARNING The device must be ...