background image

 

©

2017 WEINZIERL ENGINEERING GmbH 

Page 6/8

 

Example of assigning IP addresses 

A PC is to be used to access the KNX IP LineMaster 762. 
 
IP address of the PC: 

192.168.1.30 

Subnet of the PC:   

255.255.255.0 

The KNX IP LineMaster 762 is located in the same LAN, i.e. it 
uses the same subnet. The subnet constrains the IP addresses 
that can be assigned. In this example, the IP address of the KNX 
IP LineMaster must be 192.168.1.xx, where xx can be a number 
from 1 to 254 (with the exception of 30, which is already taken by 
the client PC). It must be ensured that no IP addresses are as-
signed twice. 

IP address of the KNX IP LineMaster 

192.168.1.31 

Subnet of the KNX IP LineMaster: 

255.255.255.0 

 

Remote access 

Remote access via Internet is possible with the KNX IP LineMas-
ter 762. More details can be found in the document "Remote ac-
cess with the ETS" at www.weinzierl.de 

 

ETS parameter dialogue 

The following parameters can be set using the ETS.

 

Device Description 

This page provides a general description of the device and the 
wiring scheme. 

 

General 

 

 

Local settings via menu 

By disabeling this option, it is no longer possible to change set-
tings via the device menu. This includes setting the IP configura-
tion, resetting the counters, the device reset, the bus reset, and 
temporarily changing the filter settings. 

Manual operation on device (bypass filtering)

 

The duration of the manual operating mode is set here. The filter 
table can be bypassed temporarily for commissioning or test pur-
poses. This can be set under the menu item "Filter". After termi-
nation, the normal operating mode as programmed by ETS is au-
tomatically processed again. 

 
Routing (KNX TP -> IP) 

 

 

 

Group telegrams (main group 0 to 13) 

Main group 0 to 13 is the standard range of group addresses in 
ETS. 

Block:

 

No group telegrams of this main group are 
routed to IP. 

Route:

 

All group telegrams of this main group are 
routed to IP independent of the filter table. 
This setting is used for testing purposes 
only. 

Filter:

 

The filter table is used to check whether or 
not the received group telegram should be 
routed to IP. 

Group telegrams (main group 14 to 31) 

Main group 14 to 31 is the extended range of group addresses in 
ETS. 

Block:

 

No group telegrams of main groups 14 to 31 
are routed to IP. 

Route:

 

All group telegrams of main groups 14 to 31 
are routed to IP. 

Filter:

 

The filter table is used to check whether or 
not the received group telegram should be 
routed to IP. 

Individually addressed telegrams  

Individual addresses are used during a download. 

Block:

 

No individually addressed telegrams are 
routed to IP. 

Route: 

All individually addressed telegrams are 
routed to IP. 

Filter:

 

The individual address is used to check 
whether the received individually addressed 
telegram should be routed to IP. 

Broadcast telegrams 

Broadcast telegrams are used when assigning individual ad-
dresses. 

Summary of Contents for KNX IP LineMaster 762

Page 1: ...coupl IP coupling of lines IP line coupler Area Backbone TP IP IP Coupling KNX Line Coupler max 15 Pcs KNX IP Router max 15 Pcs Directly via LAN Switch Main line TP TP IP Coupling KNX Line Coupler max 15x15 Pcs KNX Line Coupler max 15x15 Pcs KNX IP Router max 225 Pcs Line TP TP TP KNX IP LineMaster 762 as line coupler The individual address assigned to the KNX IP LineMaster 762 determines whether ...

Page 2: ...t of auxiliary and Bus power o The device is not loaded correctly for example a cancelled download Factory default settings The following configuration is set by factory default Individual device address 15 15 0 Number of configured KNXnet IP tunneling con 6 Individual address of tunneling con 1 15 15 240 Individual address of tunneling con 2 15 15 241 Individual address of tunneling con 3 15 15 2...

Page 3: ...owledge only when forwarding ACK acknowledge al ways NACK negative acknowledgment When answering with NACK access to the device via KNX TP is no longer pos sible see ETS parameter settings These settings are temporary Settings differing from parameterization are marked with an angular bracket The parameterized setting can be restored with a long press on Enter H Tel Counter This submenu contains t...

Page 4: ...ase section for more information As factory default the assignment of the IP address is set to au tomatically via DHCP no further IP settings are necessary To use this feature a DHCP server on the LAN must be present e g many DSL routers have an integrated DHCP server After connecting the KNX IP LineMaster 762 to the LAN it should automatically appear in the ETS within the menu Bus under Discovere...

Page 5: ...of the device Within the IP overview the IP network specific options of the KNX IP LineMaster can be changed By changing obtain an IP address automatically via DHCP to Use a static IP address static IP address the IP address sub net mask and default gateway can be set freely All changes in the properties menu become effective only after a successful application download IP address Here the IP addr...

Page 6: ...eration on device bypass filtering The duration of the manual operating mode is set here The filter table can be bypassed temporarily for commissioning or test pur poses This can be set under the menu item Filter After termi nation the normal operating mode as programmed by ETS is au tomatically processed again Routing KNX TP IP Group telegrams main group 0 to 13 Main group 0 to 13 is the standard...

Page 7: ...vidually addressed telegrams Block No individually addressed telegrams are routed to KNX TP Route All individually addressed telegrams are routed to KNX TP Filter The individual address is used to check whether the received individually addressed telegram should be routed to KNX TP Broadcast telegrams Block No received broadcast telegrams are routed to KNX TP Route All received broadcast telegrams...

Page 8: ...se direct IP connection if available in the ETS menu Bus Connections Options The download is then directly performed in the device and is not visi ble in the ETS group monitor Due to the significantly shorter transmission times it is recommended to perform downloads via IP Weinzierl Engineering GmbH D 84508 Burgkirchen Alz Germany http www weinzierl de info weinzierl de WARNING The device must be ...

Reviews: