background image

 

©

2017 WEINZIERL ENGINEERING GmbH 

Page 7/8

 

Block:

 

No received broadcast telegrams are routed 
to IP. 

Route:

 

All received broadcast telegrams are routed 
to IP. 

Acknowledge (ACK) of group telegrams 

Always:

 

A acknowledge is generated for every re-
ceived group telegram (from KNX). 

Only if routed:

 

A acknowledge is only generated for re-
ceived group telegrams (from KNX) if they 
are routed to IP. 

Acknowledge (ACK) of individually addressed telegrams 

Always: 

A acknowledge is generated for every re-
ceived individual addressed telegram (from 
KNX).

 

Only if routed:

 

A acknowledge is only generated for re-
ceived individually addressed group tele-
grams (from KNX) if they are routed to IP. 

Answer with NACK:

 Every received individually addressed tele-

gram (from KNX) is responded to with NACK 
(Not acknowledge). This means that commu-
nication with individually addressed tele-
grams on the corresponding KNX line is not 
possible. Group communication (group tele-
grams) is not affected. This setting can be 
used to block attempts at manipulation. 

When using “Answer with NACK” an access to the 
device via KNX TP is no longer possible. The 
configuration must be performed via IP. 

 

Routing (IP -> KNX TP) 

 

 

Group telegrams (main group 0 to 13) 

Block:

 

No group telegrams of these main groups 
are routed to KNX TP. 

Route:

 

All group telegrams of this main group are 
routed to KNX TP independent of the filter 
table. This setting is used for testing pur-
poses only. 

Filter:

 

The filter table is used to check whether the 
received group telegram should be routed to 
KNX TP. 

Group telegrams (main group 14 to 31) 

Block:

 

No group telegrams of main groups 14 to 31 
are routed to KNX TP. 

Route:

 

All group telegrams of the main groups 14 to 
31 are routed to KNX TP. 

Filter:

 

The filter table is used to check whether the 
received group telegram should be routed to 
KNX TP. 

Individually addressed telegrams 

Block:

 

No individually addressed telegrams are 
routed to KNX TP. 

Route:

 

All individually addressed telegrams are 
routed to KNX TP. 

Filter:

 

The individual address is used to check 
whether the received individually addressed 
telegram should be routed to KNX TP. 

Broadcast telegrams 

Block:

 

No received broadcast telegrams are routed 
to KNX TP. 

Route:

 

All received broadcast telegrams are routed 
to KNX TP. 

Resending of group telegrams 

Disable:

 

The received group telegram is not resent to 
KNX TP in case of a fault. 

Enable:

 

The received group telegram is resent up to 
three times in case of a fault. 

Resending of individually addressed telegrams  

Disable:

 

The received individually addressed tele-
gram is not resent to KNX TP in case of a 
fault. 

Enable:

 

The received individually addressed tele-
gram is resent up to three times in case of a 
fault. 

Resending of broadcast telegrams 

Disable:

 

The received broadcast telegram is not re-
sent to KNX TP in case of a fault. 

Enable:

 

The received broadcast telegram is resent 
up to three times in case of a fault. 

 

Programming 

The KNX IP LineMaster 762 can be programmed in different 
ways by the ETS: 

Via KNX Bus 

The device only needs to be connected to the KNX bus. The 
ETS requires an additional interface (for example, USB) to have 
access to the bus. Via this way both the individual address and 
the entire application including IP configuration can be pro-
grammed. Programming via the bus is recommended if no IP 
connection can be established. 

Via KNXnet/IP Tunneling 

No additional interface is required. Programming via KNXnet/IP 
Tunneling is possible if the device already has a valid IP configu-
ration (e.g. by using DHCP or Auto IP). In this case the device is 
displayed in the interface configuration of the ETS and must be 
selected. The download is executed via the ETS project as with 
many other devices. 

Via KNXnet/IP Routing 

Programming via KNXnet/IP Routing is possible if the device al-
ready has a valid IP configuration (e.g. by using DHCP or Auto 

 

Summary of Contents for KNX IP LineMaster 762

Page 1: ...coupl IP coupling of lines IP line coupler Area Backbone TP IP IP Coupling KNX Line Coupler max 15 Pcs KNX IP Router max 15 Pcs Directly via LAN Switch Main line TP TP IP Coupling KNX Line Coupler max 15x15 Pcs KNX Line Coupler max 15x15 Pcs KNX IP Router max 225 Pcs Line TP TP TP KNX IP LineMaster 762 as line coupler The individual address assigned to the KNX IP LineMaster 762 determines whether ...

Page 2: ...t of auxiliary and Bus power o The device is not loaded correctly for example a cancelled download Factory default settings The following configuration is set by factory default Individual device address 15 15 0 Number of configured KNXnet IP tunneling con 6 Individual address of tunneling con 1 15 15 240 Individual address of tunneling con 2 15 15 241 Individual address of tunneling con 3 15 15 2...

Page 3: ...owledge only when forwarding ACK acknowledge al ways NACK negative acknowledgment When answering with NACK access to the device via KNX TP is no longer pos sible see ETS parameter settings These settings are temporary Settings differing from parameterization are marked with an angular bracket The parameterized setting can be restored with a long press on Enter H Tel Counter This submenu contains t...

Page 4: ...ase section for more information As factory default the assignment of the IP address is set to au tomatically via DHCP no further IP settings are necessary To use this feature a DHCP server on the LAN must be present e g many DSL routers have an integrated DHCP server After connecting the KNX IP LineMaster 762 to the LAN it should automatically appear in the ETS within the menu Bus under Discovere...

Page 5: ...of the device Within the IP overview the IP network specific options of the KNX IP LineMaster can be changed By changing obtain an IP address automatically via DHCP to Use a static IP address static IP address the IP address sub net mask and default gateway can be set freely All changes in the properties menu become effective only after a successful application download IP address Here the IP addr...

Page 6: ...eration on device bypass filtering The duration of the manual operating mode is set here The filter table can be bypassed temporarily for commissioning or test pur poses This can be set under the menu item Filter After termi nation the normal operating mode as programmed by ETS is au tomatically processed again Routing KNX TP IP Group telegrams main group 0 to 13 Main group 0 to 13 is the standard...

Page 7: ...vidually addressed telegrams Block No individually addressed telegrams are routed to KNX TP Route All individually addressed telegrams are routed to KNX TP Filter The individual address is used to check whether the received individually addressed telegram should be routed to KNX TP Broadcast telegrams Block No received broadcast telegrams are routed to KNX TP Route All received broadcast telegrams...

Page 8: ...se direct IP connection if available in the ETS menu Bus Connections Options The download is then directly performed in the device and is not visi ble in the ETS group monitor Due to the significantly shorter transmission times it is recommended to perform downloads via IP Weinzierl Engineering GmbH D 84508 Burgkirchen Alz Germany http www weinzierl de info weinzierl de WARNING The device must be ...

Reviews: