2017 WEINZIERL ENGINEERING GmbH 

Page 8/8

 

IP). In the ETS, the routing interface appears if at least one de-
vice on the network which supports routing is available. The 
name of the network interface appears in the PC as description. 
If routing is selected as interface, the programming is done from 
the ETS project as like with other devices. In this case LAN is 
used as a KNX medium like TP. There is no additional interface 
device required. 

Via direct IP connection 

While KNXnet/IP Tunneling and KNXnet/IP Routing is limited to 
the speed of KNX TP the device can be loaded via a direct IP 
connection at high speed. The direct IP connection is possible if 
the device already has a valid IP configuration as well as an indi-
vidual address. To do this select "Use direct IP connection if 
available" in the ETS menu "Bus 

– Connections - Options". The 

download is then directly performed in the device and is not visi-
ble in the ETS group monitor. 

  

Due to the significantly shorter transmission times it is 
recommended to perform downloads via IP. 

 

 

 

 

Weinzierl Engineering GmbH

 

D-84508 Burgkirchen / Alz 

Germany 

http://www.weinzierl.de 

info@weinzierl.de

 

 

    WARNING 

 

 

The device must be mounted and commis-
sioned by an authorized electrician. 

 

The prevailing safety rules must be heeded. 

 

The device must not be opened. 

 

For planning and construction of electric in-
stallations, the relevant guidelines, regulations 
and standards of the respective country are to 
be considered. 

 

The device is a permanently connected equip-
ment: A readily accessible disconnect device 
shall be incorporated external to the equip-
ment. 

 

The installation requires a 16 A fuse for exter-
nal overcurrent protection. 

 

The power rating is indicated on the side of 
the product. 

 

 

 

Weinzierl Engineering GmbH

 

D-84508 Burgkirchen / Alz 

Germany 

http://www.weinzierl.de 

info@weinzierl.de 

2017/02/14 

 

 

Summary of Contents for KNX IP LineMaster 762

Page 1: ...coupl IP coupling of lines IP line coupler Area Backbone TP IP IP Coupling KNX Line Coupler max 15 Pcs KNX IP Router max 15 Pcs Directly via LAN Switch Main line TP TP IP Coupling KNX Line Coupler max 15x15 Pcs KNX Line Coupler max 15x15 Pcs KNX IP Router max 225 Pcs Line TP TP TP KNX IP LineMaster 762 as line coupler The individual address assigned to the KNX IP LineMaster 762 determines whether ...

Page 2: ...t of auxiliary and Bus power o The device is not loaded correctly for example a cancelled download Factory default settings The following configuration is set by factory default Individual device address 15 15 0 Number of configured KNXnet IP tunneling con 6 Individual address of tunneling con 1 15 15 240 Individual address of tunneling con 2 15 15 241 Individual address of tunneling con 3 15 15 2...

Page 3: ...owledge only when forwarding ACK acknowledge al ways NACK negative acknowledgment When answering with NACK access to the device via KNX TP is no longer pos sible see ETS parameter settings These settings are temporary Settings differing from parameterization are marked with an angular bracket The parameterized setting can be restored with a long press on Enter H Tel Counter This submenu contains t...

Page 4: ...ase section for more information As factory default the assignment of the IP address is set to au tomatically via DHCP no further IP settings are necessary To use this feature a DHCP server on the LAN must be present e g many DSL routers have an integrated DHCP server After connecting the KNX IP LineMaster 762 to the LAN it should automatically appear in the ETS within the menu Bus under Discovere...

Page 5: ...of the device Within the IP overview the IP network specific options of the KNX IP LineMaster can be changed By changing obtain an IP address automatically via DHCP to Use a static IP address static IP address the IP address sub net mask and default gateway can be set freely All changes in the properties menu become effective only after a successful application download IP address Here the IP addr...

Page 6: ...eration on device bypass filtering The duration of the manual operating mode is set here The filter table can be bypassed temporarily for commissioning or test pur poses This can be set under the menu item Filter After termi nation the normal operating mode as programmed by ETS is au tomatically processed again Routing KNX TP IP Group telegrams main group 0 to 13 Main group 0 to 13 is the standard...

Page 7: ...vidually addressed telegrams Block No individually addressed telegrams are routed to KNX TP Route All individually addressed telegrams are routed to KNX TP Filter The individual address is used to check whether the received individually addressed telegram should be routed to KNX TP Broadcast telegrams Block No received broadcast telegrams are routed to KNX TP Route All received broadcast telegrams...

Page 8: ...se direct IP connection if available in the ETS menu Bus Connections Options The download is then directly performed in the device and is not visi ble in the ETS group monitor Due to the significantly shorter transmission times it is recommended to perform downloads via IP Weinzierl Engineering GmbH D 84508 Burgkirchen Alz Germany http www weinzierl de info weinzierl de WARNING The device must be ...

Reviews: