Installation and operation manual

 

KNX PowerSupply 365

 

(Art. # 5335)

 

640 mA power supply for KNX bus 

 

 

 

KNX PowerSupply 365 

 
Application 

The KNX PowerSupply 365 is a 640 mA bus power supply with 
high efficiency and small footprint of only 4 modules (72 mm). 
The device has an integrated bus choke and also provides an 
output for auxiliary voltage. 

Three multicolor LEDs on the front indicate the condition of the 
device. They signal overload with warning, exceeding tempera-
ture and telegram traffic and the reset status. 

The two buttons enable the KNX line to be reset. 

 

Installation and commissioning 

The KNX PS 365 is mounted on a DIN rail and has a space 
requirement of 4 modules. It has the following controls (

❼❽

and displays (

❹❺❻

): 

 

 
Mains connection 

When connecting the mains voltage, the protective conductor 
(PE) must be connected, as it is used to equalize the potential of 
the bus voltage. 

Output bus voltage (KNX) 

The bus voltage is used to supply KNX devices for the medium 
twisted pair. The integrated bus choke separates the DC supply 
voltage from the bus signals. 

 

 

Output auxiliary voltage (30 V) 

This output is used to supply additional equipment. The output is 
galvanically connected to the bus voltage, but is not at the same 
potential. This means that "minus" bus and "minus" of the auxil-
iary voltage are not the same and must not be connected to 
each other. If required, the auxiliary voltage can be routed to the 
load via the second wire pair (yellow / white) of the KNX cable. 

All data on the output current relate, unless otherwise stated, to 
the sum of the currents of bus voltage and auxiliary voltage. 

 

Settings 

The device requires no settings and does not occupy any KNX 
addresses. 

 

Display of the status LED

 

❹❺❻

 

 

 

 

 

 

LED „Current“ 
output 

Meaning 

LED lights green 

The device operates in normal operating mode. 
Sum of the output currents < 600 mA 

LED lights yellow 

The device operates in normal operating mode. 
Sum of the output currents 600 mA < I < 640 mA 

LED lights red 

overcurrent 
Sum of the output currents I > 640 mA 

LED flashes red 

Critical overcurrent 
Sum of the output currents I > 900 mA 

LED „Temp.“ 
temperature 

Meaning 

LED lights green 

The device operates in normal operating mode. 
Temperature in the housing < 60 ° C 

LED lights yellow 

The device operates in normal operating mode. 
Temperature in housing > 60 ° C and < 75 ° C 

LED lights red 

Overtemperature 
Temperature in the housing > 75 ° C 

LED flashes red 

Critical overtemperature 

LED off 

If the temperature increases further, the unit switches 
off for safety reasons. In this case, a display on the 
device is no longer possible.  
To restart, the unit must cool down and be discon-
nected from the mains for a short time (about 10 s). 
 

LED „Traffic/ 
Reset“ 
 

Meaning 

LED lights green 

No telegram traffic 

LED flickers green 

Telegram traffic with bus load < 70% 

LED flickers yellow 

Telegram traffic with bus load > 70% 

LED lights red 

Reset active 
Can be stopped manually or automatically. 

EN 

 Aux. Power Out 30 V DC 

 

KNX Bus Out 

 

Power in 230 V AC 

 LED „Current“ 

 LED „Temp.“ 

(Temperature) 

 LED “Traffic/Reset” 

 Button Reset Start 

 Button Reset Stop 