1. 

Direct setting/status display on device 

A.  Startup and idle display 

During startup of the device, the physical 
address and the status of the application 
is displayed. 
The device name “KNX PS 367” can be 
changed within ETS parameter settings. 

The status can be one of the following values: 

 

Running:

 Application is loaded and running 

 

Stopped:

 The application is stopped- 

 

LED for 

Programming Mode is flashing 

 

Unloaded: 

The application is not loaded - 

 

LED 

for Programming Mode is flashing 

 

Loading:

 The application is currently loading 

 

Overload:

 The output current is above the max. 

limit (900mA) - 

 

LED for Programming Mode is 

flashing 

 

USB:

 USB Connection established  

 

USB local:

 local download via USB is executed 

The power supply functionality (KNX and auxiliary voltage) is 
not dependent whether the application is running or not. 

After 10 minutes of inactivity the display will turn into 
screensaver mode (blank screen with a bouncing dot) to 
safe display life time. Press any key to turn the display 
on again. The activation of the display can be synchro-
nized between all devices of this device line of Weinzierl 
via a group object. See parameter section for details. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

 

 

 

 

 

 

Local download via USB 

The internal application can be loaded both with an additional 
interface via the KNX bus or locally via the integrated USB inter-
face. When using an additional interface the download is done 
conventionally but there may not be any USB connection on 
KNX Power Supply USB 367. 

For local download via the integrated USB interface, the follow-
ing differences should be noted: 

 

Reaction with the ETS 5.5 

via ETS menu 

“connection/interfaces” 

Physical address 

Possible without programming 
mode but no automatic adoption 

into ETS project (see picture of 
ETS below)  

via projec

t “programming“ 

Physical address &  

application program  

The complete download is 
executed over the bus at slow 

speed. The change of the physi-
cal address may not be taken 

over with the connection and 
may cause inconsistencies later 

on.  

Partial 

The download is executed 
automatically at high speed. 

Physical address 

The download is executed over 
the bus. 

The change of the physical 
address may not be taken over 

with the connection. 

Application program 

The download is executed 
automatically at high speed. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The integrated USB Interface does not support the bus 
monitor mode.

  

 

 

 

 

 

Setting of local addresses 
in the ETS menu “connec-
tion / Interfaces”

  

 

Local download in the ETS 5.5  

 

Summary of Contents for KNX PowerSupply USB 367

Page 1: ...ly KNX devices for the medium twisted pair The integrated bus choke separates the DC supply voltage from the bus signals Output auxiliary voltage 30 V This output is used to supply additional equipment The output is galvanically connected to the bus voltage but is not at the same potential This means that minus bus and minus of the auxil iary voltage are not the same and must not be connected to e...

Page 2: ... line of Weinzierl via a group object See parameter section for details Local download via USB The internal application can be loaded both with an additional interface via the KNX bus or locally via the integrated USB inter face When using an additional interface the download is done conventionally but there may not be any USB connection on KNX Power Supply USB 367 For local download via the integ...

Page 3: ...f the KNX voltage The default reset time is 30 seconds To stop the count down press escape G Submenu System Info This submenu displays information about the device serial number SN App ID App status App ST and Firm ware Revision Fw Rev H Sub menu Counters The operating status is logged automatically in the device and can be viewed in this sub menu All times as displayed in the format h m Operation...

Page 4: ... start To stop countdown press en ter again during countdown N Timer Switch on and off delay Timer that switches ON OFF after de fined duration in seconds set via the ETS After pressing enter count down will start and the timer will turn on After first countdown is finished press enter again to start countdown to turn off To stop countdown press enter again during countdown O Timer Impulse Stairca...

Page 5: ...er appears Each Weinzierl device with a display of this product range pro vides this parameter As soon as the device wakes up the asso ciated group telegram will be sent to the KNX bus which wakes up every other device whose display synchronization group object is associated to the same group address Operating control Enabled Disabled If enabled a parameter Cycle time 10 s 24 h and a group object ...

Page 6: ...cs values will be sent to the bus If Reset max values is triggered the values of diagnostic ob jects Current max and Temperature max are reset to the actual values and sent to the bus for confirmation B Alarm This parameter sets basic alarm functions Send alarm Disabled No group object for alarm states are available Send alarm On alarm On alarm and alarm end If activated the alarm state group obje...

Page 7: ... duration defined in Delay time s parameter The output value can be inverted by parameter Output Not inverted Inverted Input 1 0 Output 1 T 0 Each timer can be stopped by sending the opposite val ue to its input group object For example An already started switch on timer can be stopped by sending OFF 0 to its input group object Function type Logic The logic specific parameters and group objects ar...

Page 8: ...which is used by ETS is 55 This length has been specified as require ment for new KNX system devices An APDU length of 55 results in total length of a KNX telegram on twisted pair of 64 bytes and occupies the bus for about 90 ms The download is much faster if the USB interface is in stalled in the same line as the target device With each line coupler in between the download time growths Group Obje...

Reviews: