T.  Logic NOR gate 

The output is triggered on (1) if both in-
puts are switched off (0). 

 

Input A 

Input B 

Output 

 

U.  Logic XNOR gate 

The output is triggered on (1) if both in-
puts are equal. 

 

Input A 

Input B 

Output 

 
 

V.  Logic INVERTER 

Input on (1) is converted into output off 
(0). Input off (0) is converted into output 
on (1). 

 

Input  

Output 

 

 

 

 

 

 

 

 

 

 

 

 

 

2. ETS Setup 

The ETS database entry (ETS 4.2 and ETS 5) can be down-
loaded on the KNX PowerSupply 366 product website 
(www.weinzierl.de). 

A. 

General 

 

 

 

 

 

 

 

This parameter allows setting of general functions of the device:  

Device name (free text input) 

The device name can be chosen freely. The maximum length of 
the name is 30 characters. After the ETS application download 
the name will be shown within the devices startup and idle dis-
play. 

Display synchronization (Enabled / Disabled) 

If enabled, a communication object  
‘Display synchronization – Trigger’ appears. 
Each Weinzierl device with a display of this product range pro-
vides this parameter. As soon as the device wakes up, the asso-
ciated group telegram will be sent to the KNX bus which wakes 
up every other device whose display synchronization group 
object is associated to the same group address. 

 

Operating control (Enabled / Disabled) 

If enabled, 

a parameter ‘Cycle time’ (10 s – 24 h) and a group 

object ‘Operating control – Monitor’ appears. This group object 
allows to implement a ‘heart beat’. If associated with a group 
address, the group telegram will be sent to the KNX bus accord-
ing to the set ‘Cycle time’. 
The telegram can then be used to detect whether the device is 
still connected and working. 

 

Bus reset via object (Enabled / Disabled) 

If enabled, the parameter provides the 

group object ‘Bus reset – 

Trigger’. If associated with a group address a bus reset can be 
forced by sending a group telegram. 

 

 

 

Group Object 

Type KNX 

Size 

Direction 

1: Display synchronization 

– Trigger 

1.017 

1 Bit 

From / To KNX 

Group Object 

Type KNX 

Size 

Direction 

2: Operating control 

– Monitor 

1.017 

1 Bit 

To KNX 

Group Object 

Type KNX 

Size 

Direction 

3: Bus reset 

– Trigger 

1.017 

1 Bit 

To KNX 

 

 

 

 

Summary of Contents for KNX PowerSupply USB 367

Page 1: ...ly KNX devices for the medium twisted pair The integrated bus choke separates the DC supply voltage from the bus signals Output auxiliary voltage 30 V This output is used to supply additional equipment The output is galvanically connected to the bus voltage but is not at the same potential This means that minus bus and minus of the auxil iary voltage are not the same and must not be connected to e...

Page 2: ... line of Weinzierl via a group object See parameter section for details Local download via USB The internal application can be loaded both with an additional interface via the KNX bus or locally via the integrated USB inter face When using an additional interface the download is done conventionally but there may not be any USB connection on KNX Power Supply USB 367 For local download via the integ...

Page 3: ...f the KNX voltage The default reset time is 30 seconds To stop the count down press escape G Submenu System Info This submenu displays information about the device serial number SN App ID App status App ST and Firm ware Revision Fw Rev H Sub menu Counters The operating status is logged automatically in the device and can be viewed in this sub menu All times as displayed in the format h m Operation...

Page 4: ... start To stop countdown press en ter again during countdown N Timer Switch on and off delay Timer that switches ON OFF after de fined duration in seconds set via the ETS After pressing enter count down will start and the timer will turn on After first countdown is finished press enter again to start countdown to turn off To stop countdown press enter again during countdown O Timer Impulse Stairca...

Page 5: ...er appears Each Weinzierl device with a display of this product range pro vides this parameter As soon as the device wakes up the asso ciated group telegram will be sent to the KNX bus which wakes up every other device whose display synchronization group object is associated to the same group address Operating control Enabled Disabled If enabled a parameter Cycle time 10 s 24 h and a group object ...

Page 6: ...cs values will be sent to the bus If Reset max values is triggered the values of diagnostic ob jects Current max and Temperature max are reset to the actual values and sent to the bus for confirmation B Alarm This parameter sets basic alarm functions Send alarm Disabled No group object for alarm states are available Send alarm On alarm On alarm and alarm end If activated the alarm state group obje...

Page 7: ... duration defined in Delay time s parameter The output value can be inverted by parameter Output Not inverted Inverted Input 1 0 Output 1 T 0 Each timer can be stopped by sending the opposite val ue to its input group object For example An already started switch on timer can be stopped by sending OFF 0 to its input group object Function type Logic The logic specific parameters and group objects ar...

Page 8: ...which is used by ETS is 55 This length has been specified as require ment for new KNX system devices An APDU length of 55 results in total length of a KNX telegram on twisted pair of 64 bytes and occupies the bus for about 90 ms The download is much faster if the USB interface is in stalled in the same line as the target device With each line coupler in between the download time growths Group Obje...

Reviews: