background image

©

2019 WEINZIERL ENGINEERING GmbH 

Page 6/8

 

Wait to send after bus voltage recovery (Enabled / Disabled) 

If enabled, the 

parameter ‘Waiting time’ (10 s – 120 s) appears. 

The set value determines the waiting time, until diagnostic tele-
grams will be sent after bus voltage recovery. The telegrams of 
the following group objects will be restrained: 
- Diagnostics 

– Voltage [V] – Value 

- Diagnostics 

– Current [A] – Value 

- Diagnostics 

– Current max. – Value 

- Diagnostics 

– Temperature [°C] – Value 

- Diagnostics 

– Temperature max. – Value 

- Diagnostics 

– Busload [%] – Value

 

Device reset via menu (Enabled / Disabled) 

By disabling this option, the function for resetting the device by 
its local menu is deactivated. 
 

Diagnostics 

 

 

 

 

 

 

This parameter sets basic diagnostic functions. 

 

Send diagnostic values (Disabled) 

No group objects for diagnostic values are available. 

Send diagnostic values (Cyclic) 

The group object for diagnostic values are available. 
The associated group telegrams will be sent in dependence of 
the set cycle time. 

Send diagnostic values (On change) 

The group objects for diagnostic values are available. 
The group telegrams will only be sent if the value changes. 

Send diagnostic values (Cyclic and on change) 

The group objects for diagnostic values are available. 
The group telegrams will be sent in dependence of the set cycle 
time as well as when the value changes. 

Send diagnostic values (On request only) 

The group objects for diagnostic values are available. 
The telegrams will only be sent if triggered by a telegram to 
group object 
- Diagnostics 

– Request values – Trigger. 

If the diagnostic values are activated, the group objects 
- Diagnostics 

– Request values – Trigger 

- Diagnostics 

– Reset max. values – Trigger 

are always available. 
If a group telegram is sent to 

‘request values trigger’ all diagnos-

tics values will be sent to the bus. 
If 

‘Reset max. values’ is triggered, the values of diagnostic ob-

jects “Current max.” and “Temperature max.” are reset to the 
actual values and sent to the bus for confirmation. 

 
 

B. 

Alarm 

 

 

 

 

 

 

This parameter sets basic alarm functions. 

 

Send alarm (Disabled) 

No group object for alarm states are available. 

Send alarm (On alarm / On alarm and alarm end) 

If activated the alarm state group objects as well as the threshold 
options appear.  
‘Threshold current min. [mA]’ option declares the minimum 
amount of current. If the actual current falls below the chosen 
threshold, the message associated to group object  
‘Alarm – Current min. – State’ will be sent.  
‘Threshold current max. [mA]’ option declares the maximum 
amount of current. If the actual current rises above the chosen 
threshold, the message associated to group object  
‘Alarm – Current max. – State’ will be sent.  
‘Threshold temperature [°C]’ determines the maximum of al-
lowed temperature. If the actual temperature within the housing 
rises above the chosen threshold, the message associated to 
group objec

t ‘Alarm - Temperature – State’ will be sent. 

 
If the actual values 

return into the ‘no alarm zone’ only a mes-

sage will be sent if option ‘On alarm and alarm end’ is chosen.

 

 

The measured current is the combined value of bus 
and auxiliary output. 

 

Group Object 

Type KNX  Size 

Direction 

11: Diagnostics 

– Request values - Trigger 

1.017 

1 Bit 

From KNX 

12: Diagnostics 

– Reset max. values - 

Trigger 

1.017 

1 Bit 

From KNX 

13: Diagnostics 

– Voltage [V] - Value 

14.027 

4 Byte 

To KNX 

14: Diagnostics 

– Current [A] - Value 

14.019 

4 Byte 

To KNX 

15: Diagnostics 

– Current max. [A] - Value 

14.019 

4 Byte 

To KNX 

16: Diagnostics 

– Temperature [°C] - Value 

9.001 

2 Byte 

To KNX 

17: Diagnostics 

– Temperature max. [°C] - 

Value 

9.001 

2 Byte 

To KNX 

18: Diagnostics 

– Busload [%] - Value 

5.001 

8 Bit 

To KNX 

Group Object 

Type KNX 

Size 

Direction 

20: Alarm 

– Current min. - State 

1.005 

1 Bit 

To KNX 

21: Alarm 

– Current max. - State 

1.005 

1 Bit 

To KNX 

22: Alarm 

– Temperature – State 

1.005 

1 Bit 

To KNX 

 

 

 

 

 

Summary of Contents for KNX PowerSupply USB 367

Page 1: ...ly KNX devices for the medium twisted pair The integrated bus choke separates the DC supply voltage from the bus signals Output auxiliary voltage 30 V This output is used to supply additional equipment The output is galvanically connected to the bus voltage but is not at the same potential This means that minus bus and minus of the auxil iary voltage are not the same and must not be connected to e...

Page 2: ... line of Weinzierl via a group object See parameter section for details Local download via USB The internal application can be loaded both with an additional interface via the KNX bus or locally via the integrated USB inter face When using an additional interface the download is done conventionally but there may not be any USB connection on KNX Power Supply USB 367 For local download via the integ...

Page 3: ...f the KNX voltage The default reset time is 30 seconds To stop the count down press escape G Submenu System Info This submenu displays information about the device serial number SN App ID App status App ST and Firm ware Revision Fw Rev H Sub menu Counters The operating status is logged automatically in the device and can be viewed in this sub menu All times as displayed in the format h m Operation...

Page 4: ... start To stop countdown press en ter again during countdown N Timer Switch on and off delay Timer that switches ON OFF after de fined duration in seconds set via the ETS After pressing enter count down will start and the timer will turn on After first countdown is finished press enter again to start countdown to turn off To stop countdown press enter again during countdown O Timer Impulse Stairca...

Page 5: ...er appears Each Weinzierl device with a display of this product range pro vides this parameter As soon as the device wakes up the asso ciated group telegram will be sent to the KNX bus which wakes up every other device whose display synchronization group object is associated to the same group address Operating control Enabled Disabled If enabled a parameter Cycle time 10 s 24 h and a group object ...

Page 6: ...cs values will be sent to the bus If Reset max values is triggered the values of diagnostic ob jects Current max and Temperature max are reset to the actual values and sent to the bus for confirmation B Alarm This parameter sets basic alarm functions Send alarm Disabled No group object for alarm states are available Send alarm On alarm On alarm and alarm end If activated the alarm state group obje...

Page 7: ... duration defined in Delay time s parameter The output value can be inverted by parameter Output Not inverted Inverted Input 1 0 Output 1 T 0 Each timer can be stopped by sending the opposite val ue to its input group object For example An already started switch on timer can be stopped by sending OFF 0 to its input group object Function type Logic The logic specific parameters and group objects ar...

Page 8: ...which is used by ETS is 55 This length has been specified as require ment for new KNX system devices An APDU length of 55 results in total length of a KNX telegram on twisted pair of 64 bytes and occupies the bus for about 90 ms The download is much faster if the USB interface is in stalled in the same line as the target device With each line coupler in between the download time growths Group Obje...

Reviews: