Figure 6-9 - MPM & PSU installed on mounting plate
4. If SIM card has not been installed, insert this now into J15 on the MPM. The
protective shroud needs to be removed to do this (needs Torx T27 driver). Be sure to
re-install the protective cap afterwards.
Figure 6-10 SIM card receptacle in MPM
5. Connect 24Vdc power lead (PN# LFS04875-012M00) from PSM J2 into DC power
input port (J14) on MPM
Figure 6-11 24Vdc power connection from PSM to MPM
6. Ensure the customer mains outlet is either isolated or turned off and locked
7. Connect the mains power lead from the customer power outlet to the AC input port J1
on the PSM using cable PN# LFS04876.
J2