Figure 6-12 Mains AC power connection to PSM
8. Locking clips need to be installed on the power supply connectors for hazardous
location compliance. These locking clips shall only be removed by qualified service
personnel. The installation of these clips is as follows:
Figure 6-13 Installation of Locking Clips
WARNING
: EXPLOSION HAZARD. DO NOT CONNECT OR DISCONNECT CABLES
WHEN ENERGIZED IN A HAZARDOUS LOCATION ENVIRONMENT.
AVERTISSEMENT
: RISQUE D'EXPLOSION. NE PAS CONNECTER OU DÉCONNECTER
DES CÂBLES QUI ENERGISES DANS UN ENVIRONNEMENT DE LOCALISATION
DANGEREUSE.
9. Protective earth grounding of the system is provided by the earth ground connection
from the power supply AC cable, and connection of the enclosures of the MPM and
PSM to earth ground is optional.
11.2.310.2.3
Hazardous Location Requirements
The enclosure of the power supply and the MPM will need to be grounded to earth ground
according to local building codes for hazardous location use. The back side of the power
supply is bare metal, allowing it to be grounded to the mounting plate when it is bolted in
place. The mounting plate will need to have no coating where the power supply is installed
in order to provide electrical conductivity.