8.) Green LED 4
– I/O Status
12.511.5
Installation
This section covers the generic installation process for the RSP. It is important to note that
product specific installation such as sensors, junctions boxes etc will only be covered
generically and product specific instructions are covered in the IOM Manual.
12.5.111.5.1
Physical mounting
The mounting dimensions are as follows. Use M10 bolts to fasten the RSP to the
mounting location.
Figure 11-7 RSP Mounting Dimensions
12.5.211.5.2
Hazardous Location Compliance
The enclosure of the RSP will need to be grounded to earth ground according to local
building codes for hazardous location use. The RSP has an M6 sized external grounding
screw for protective earth grounding. Insulated 10AWG wiring is needed to connect this
grounding screw to the mounting plate, along with the use of M6 sized ring connectors for
10AWG wire. The connection to the mounting plate should be made using a lock washer or
lock nut to ensure that the connection cannot loosen from vibration. If this mounting plate is
not directly connected to earth ground through the machinery then the mounting plate will
also need to be grounded to earth with the use of 10AWG wire and ring connectors.