2.3.1 Keypad-entered Fields
Clicking or pressing in a text box launches a keypad or keyboard for user input. The previous value is loaded as the default so that
clicking outside of the keypad or clicking
Accept
without entering anything will cancel the action and close the keypad.
To apply a new value, type it in with the keypad and click
Accept
. The
input will be validated, and if it falls outside an allowed range it will be
coerced to the closest acceptable value. A warning box indicates user
entry errors. When a valid entry is made, a popup message confirms the change.
Limits are enforced when choosing set points. These thresholds are
configurable in the Settings page, with a login.
2.3.2 Dump Switch
The switch on the far right is the dump switch. It has two positions: Auto and Manual Dump. When the dump switch is in the Auto
position the system maintains sufficient nitrogen pressure to hold the relief valve closed until the pop-off conditions are met.
Toggle between
Auto
and
Manual Dump
by clicking or touching the on-screen switch. When
Manual Dump
is activated, any nitrogen
pressure in the dome is immediately vented and the relief valve opens to vent the process pressure. The user is prompted to confirm
before the action is taken.
The dump switch operates the same as the physical switch on the suitcase; however, when the physical switch is in the
Manual Dump
position, the software dump switch is disabled as shown below.