Installation and operating instruction
Oil burner WL5-PB-H purflam®
3 Product description
83242002 1/2019-03 La
16-76
3.4.6 Rating
Combustion heat rating
The ratings range depends on:
Size of mixing head (1. or 2.)
Diameter of air nozzle (19 … 25 mm)
Mixing head
Combustion heat rating
[kW]
Oil throughput [kg/h]
ME 1.19
16.5 … 20.0
1.4 … 1.7
ME 1.21
20.0 … 24.0
1.7 … 2.0
ME 1.22
23.0 … 26.5
1.9 … 2.2
ME 1.23
26.0 … 29.0
2.1 … 2.4
ME 1.24
28.0 … 32.0
2.3 … 2.7
ME 2.24
31.0 … 35.0
2.6 … 2.9
ME 2.25
34.0 … 40.0
2.9 … 3.4
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
-0.1
-0.2
-0.3
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
1.4
1.2
1.6
2.0
1.8
2.2
2.4
2.6
2.8
3.0
3.2
3.4
1.19
1.22
1.24
2.24
1.21
1.23
2.25
2
1
1
Combustion heat rating [kW] or [kg/h]
2
Combustion chamber pressure [mbar]