63
9
CODE Message Cause
Possible
fault/rectification
Electronic
compound
regulation
61
Fault
Deviation of ionisation signal to
• Wrong setting of gas type at gas valve,
setpoint too large
check setting
• Parameter P11 set to wrong gas type
• Check resistance ionisation circuit -
R > 50 k
Ω
➩
replace cable
• Ionisation electrode soild or mechanically deformed
• WCM-CPU faulty - replace
62
Fault
The setting signal of the gas
• As F61
setting element exceeds the
• Check flue gas circulation - flue gas system is
permissible tolerance range
gas tight
➩
Ch. 5.5
• Fan does not achieve min. speed in controlled
operation
• Flue gas side resistance too high -
check condensate outlet
• Insufficient gas pressure
64
Fault
New calibration value exceeds
• Check flue gas circulation - flue gas system is
factory preset limits
gas tight
➩
Ch. 5.5
• External influences on the unit (supply air) due to
flue gas, dust or other contaminants
65
Fault
New calibration value deviates too
• Supply air contaminated by dust and soot
much from the previous value
• 100% calibration was not carried out following
the repalcement of SCOT electrode,
WCM-CPU or burner (
➩
Ch. 5.5, P39)
66
Fault
Contrary to requirements
• Ignition occurs too late - increase P35 (see F21)
calibration was not carried out
• External influences on the unit e.g. by dust, flue
gas or on twin flue systems by soot
• Deviations in the gas quality - carry out 100%
calibration
• Follow on fault from F22
67
Fault
The setpoint was incorrectly saved
• Incorrect commissioning with liquid petroleum gas,
i.e. P11 was set to natural gas
• Replace WCM-CPU
• Insufficient gas supply, gas pressure drops
Continuation of fault and warning message