6.5.2 Menu structure heating engineer level DHW
Depending on the scope of the system some parameters may not be displayed
Menu point
Parame-
ters
Description
Factory pre-
setting
Set
Commissioning
P311
Language
German
System info
P331
External
current
°C
dampened
°C
mixed
°C
P332
Config WTC-G
–
P334
Config user
–
P335
Config FS
–
P336
Config EM#X
–
P337
Setpoint temp system
°C
P338
Error history
–
P339
Version WCM-FS
–
P340
Version SOL
–
P341
Version EM-DHW
–
Heating circuit
Exten-
sion
module
#X
P402
H1-Fct DHW
Standby
P404
Output test
DHW
–
Heating
circuit
info
P522
Room temp
°C
P524
DHW
°C
-
Circ temp
°C
DHW
P601
DHW maximum
60°C
P602
DHW switch diff
-3.0K
P603
DHW boost
15K
P604
Max DHW load time
10 min
P605
Legio fct
Friday
P606
Antileg setpoint temp
60.0°C
P607
Legio time
22 hrs
P608
Circ during Legio
Off
P609
Circ time
3 min
P610
Circ temp
30.0°C
P611
SOL yield DHW
Off
Access HC without
FS
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
6 Operation
83277502 • 3/2012-10 • La
39-106
Summary of Contents for WCM-EM 2.1
Page 107: ...83277502 3 2012 10 La ...