6.5.5 Configuration of the WTC heat exchanger
This parameter is used to transfer the configuration information from the condensing
boiler to the WCM-FS.
Heat exchanger
Config WTC ... #1
Unit type, load and eBUS address of the heat exchanger
Hydraulic version
DHW
WTC, vers. -W (water heater)
sensor B3 installed in the unit
Heating appliance
WTC, vers. -H
Combi
WTC, vers. -C DHW preparation via plate heat exchanger
Integra
WTC, vers. -K with WAI
Power
WTC, vers. -K with WAP
External sensor
External sensor
External sensor B1 installed
Control variation
Buffer 1
Buffer control with sensor B10
Buffer 2
Buffer control with 2 sensors B10 + B11
De-couple
De-couple control with sensor B11
▶
Activate heating engineer level (see Ch. 6.5).
▶
Press function key
System info
.
✓
Menu
System info
is displayed.
▶
Press function key
Config WTC-G …#1
and, where applicable,
Config WTC-
O …#1
.
✓
Parameter
Config WTC-G …#1
and, where applicable,
Config WTC-O …#1
is displayed.
▶
Check, if configuration WCM-FS and WTC are the same
(WTC parameter
10
heating engineer level).
▶
If the configuration is not the same, press function key
New
.
✓
The message
search config
appears briefly, then the current configuration is
displayed.
▶
Exit menu using function key
End
.
01
01
Heating engineer
System info
Commissioning
System info
Heating circuit #1
End
End
-
+
Config WTC-G ..#1
332
End
New
External
Config WTC-G ..#1
Config FS
DHW
External sensor
Buffer 2
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
6 Operation
83277502 • 3/2012-10 • La
43-106