6.5.17 Set mixer parameters
Only on heating circuit with mixer (supply sensor B6 fitted to WCM-EM).
This parameter is used to match the WCM-EM to the mixer.
The value (temperature in K) defines the regulating range within which the signal is
given in linear impulses. In addition the control impulse is "Continually open" or "Con-
tinually closed".
▶
Activate heating engineer level (see Ch. 6.5).
▶
Press function key
Heating circuit
.
▶
Press function key
Setting #2
.
✓
Menu
Setting #2
is displayed.
▶
Press function key
Mixer parameter
.
✓
Parameter
Mixer parameter
is displayed.
▶
Set value using the dial knob and save with function key
OK
.
02
Setting #2
Boil.MC boost
2.0K
Mixer parameter 8.0K
min pump speed
50%
End
-
+
Mixer parameter
465
End
Standard
OK
8.0K
1.0K - 24.0K
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
6 Operation
83277502 • 3/2012-10 • La
57-106
Summary of Contents for WCM-EM 2.1
Page 107: ...83277502 3 2012 10 La ...