6.5.18 Set frost protection
This parameter is only displayed if a separate external sensor has been connected to
connection B1 (zone control).
Heating circuit pump
On
current external temperature < parameter 426 - 5 K
current external temperature < parameter 466 - 5 K (HC #1
+2)
Heating circuit pump
Off
current external temperature > parameter 426
current external temperature > parameter 466 (HC #1+2)
▶
Activate heating engineer level (see Ch. 6.5).
▶
Press function key
Heating circuit
.
▶
Press function key
Setting #2
.
✓
Menu
Setting #2
is displayed.
▶
Press function key
Frost protection
.
✓
Parameter
Frost protection
is displayed.
▶
Set value using the dial knob and save with function key
OK
.
02
Setting #2
Boiler-MC boost
2.0K
Mixer parameter 8.0K
Frost protection
5.0°C
End
-
+
Frost protection
426
End
Standard
OK
5.0°C
-10.0°C - 10.0°C
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
6 Operation
83277502 • 3/2012-10 • La
58-106
Summary of Contents for WCM-EM 2.1
Page 107: ...83277502 3 2012 10 La ...