6.5.25 Function specific heating
Test function of underfloor heating and stress test for the screed, this is not a drying
function.
▶
Press function key
Days Min.Temp.Fht
.
✓
Parameter
Days Min.Temp.Fht
is displayed.
▶
Make selection using the dial knob and save with function key
OK
.
02
Screed #2
Days Min Temp Fht
05
Max Temp Fht
45.0°C
Days Max Temp Fht
04
End
-
+
Days Min Temp Fht
444
End
Standard
OK
02 - 30
05
Set stress phase
The setpoint of the screed function is limited to 60°C. If the maximum supply tem-
perature is set below 60°C, the limit is set to this value.
▶
Press function key
Max.Temp.Fht
.
✓
Parameter
Max.Temp.Fht
is displayed.
▶
Make selection using the dial knob and save with function key
OK
.
-
+
Max Temp Fht
445
End
Standard
OK
35.0°C - 60.0°C
45.0°C
02
Screed #2
Days min temp Fht
05
Max Temp Fht
45.0°C
Days Max Temp Fht
04
End
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
6 Operation
83277502 • 3/2012-10 • La
70-106