6.5.29 Set switch on optimisation
This parameter is only displayed, if room or weather compensation has been activated
in level Type of control#1 (see Ch. 6.5.8).
To ensure the room setpoint temperature has been reached at the beginning of normal
operation (heating program), the switch on time is preset. The parameter
On Opti
limits the maximum time of the pre-setting. At
Curr
the current pre-set time calculated
is displayed.
Room dependent variation (pre-setting based on the actual room temperature)
Setting parameter
318 Room
or
The optimisation function is reset to the maximum value:
▪
after resetting of the WCM-FS,
▪
after resetting of parameter via function key 2,
▪
after changing parameter heating circuit type (P316).
Weather dependent variation (pre-setting based on the external temperature)
Setting parameter
Setting range
Off
00:15
…
04:00 h
▶
Activate heating engineer level (see Ch. 6.5).
▶
Press function key
Heating circuit
.
▶
Press function key
Control behaviour
.
✓
Menu
Control behaviour
is displayed.
▶
Press function key
On Opti
.
✓
Parameter
On Opti
is displayed.
▶
Set value using the dial knob and save with function key
OK
.
01
Control behaviour
Reduced oper. Setback
Frost limit
Off
On Opti
End
-
+
On Opti
503
End
Reset
Standard
OK
--;00:15 - 04:00
Act
----
Max
02:00h
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
6 Operation
83277502 • 3/2012-10 • La
76-106
Summary of Contents for WCM-EM 2.1
Page 107: ...83277502 3 2012 10 La ...