Installation and Operating Manual
Data protocol converter Gateway WEM-KNX
7 Operation
83320602
▪ 1/202
1-02
▪
Ext. PHauner
21-36
Object name
Object function
Data type C R W T U Actualiz.
Pre-flow set
temperature
Special level
DPT9.001 X X X X X
m(≥60s)
Su/Wi change-over
Function/Off
DPT1.002 X X X X X
m(≥60s)
Su/Wi change-over
Function/On
DPT1.002 X X X X X
m(≥60s)
Actual Operating mode System Standby
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode System Summer
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode Screed:
Function heating
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode Screed:
Laying heating
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode Holiday
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode Time program 1
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode Time program 2
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode Time program 3
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode Summer
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode Night setback
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode Normal
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode Comfort
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode Standby
DPT1.002 X X - X -
m(≥60s)
Status Heating circuit 1 Room frost protection DPT1.002 X X - X -
m(≥60s)
Status Heating circuit 1 Plant frost protection DPT1.002 X X - X -
m(≥60s)
Status Heating circuit 1 Input H1: Special
DPT1.002 X X - X -
m(≥60s)
Status Heating circuit 1 Input H1: Comfort
DPT1.002 X X - X -
m(≥60s)
Status Heating circuit 1 Input H1: Normal
DPT1.002 X X - X -
m(≥60s)
Status Heating circuit 1 Input H1:
Night setback
DPT1.002 X X - X -
m(≥60s)
Status Heating circuit 1 Input H1: Standby
DPT1.002 X X - X -
m(≥60s)
Status Heating circuit 1 Input H1:
Emergency-Off
DPT1.002 X X - X -
m(≥60s)
Status Heating circuit 1 Party
DPT1.002 X X - X -
m(≥60s)
Status Heating circuit 1 Optimization
DPT1.002 X X - X -
m(≥60s)
Status Heating circuit 1 Level increase
Outside temperature
DPT1.002 X X - X -
m(≥60s)
Status Heating circuit 1 Ext. Emergency
acceptance
DPT1.002 X X - X -
m(≥60s)
Status Heating circuit 1 Ext. Oversupply
DPT1.002 X X - X -
m(≥60s)
Status Heating circuit 1 Ext. Heating
specification
DPT1.002 X X - X -
m(≥60s)
Status Heating circuit 1 Warm water priority
DPT1.002 X X - X -
m(≥60s)
Status Heating circuit 1 Summer operation
weather-guided
DPT1.002 X X - X -
m(≥60s)
Status Heating circuit 1 Heating limit Room
DPT1.002 X X - X -
m(≥60s)
Status Heating circuit 1 Heating limit VL
DPT1.002 X X - X -
m(≥60s)
Status Heating circuit 1 Room thermostat
DPT1.002 X X - X -
m(≥60s)