Installation and Operating Manual
Data protocol converter Gateway WEM-KNX
7 Operation
83320602
▪ 1/202
1-02
▪
Ext. PHauner
25-36
7.4.9
Communication objects for EM-WW
Object name
Object function
Data type C R W T U Actualiz.
WW set temperature
Normal
DPT9.001 X X X X X
m(≥60s)
WW set temperature
Night setback
DPT9.001 X X X X X
m(≥60s)
Warm water push
Start
DPT1.002 X X X X X
s(≥10s)
Warm water
temperature
Actual value
DPT9.001 X X - X -
s(≥10s)
Status
Standby: no heating
circuit active
DPT1.002 X X - X -
m(≥60s)
Status
Time program -
Normal
DPT1.002 X X - X -
m(≥60s)
Status
Time program -
Night setback
DPT1.002 X X - X -
m(≥60s)
Status
Warm water charge
active
DPT1.002 X X - X -
m(≥60s)
Status
Service
DPT1.002 X X - X -
m(≥60s)
Status
Overtemperature
Alternative energy
DPT1.002 X X - X -
m(≥60s)
Status
Surplus
Alternative energy
DPT1.002 X X - X -
m(≥60s)
Status
Acceptance WW
Alternative energy
DPT1.002 X X - X -
m(≥60s)
Status
Frost protection
active
DPT1.002 X X - X -
m(≥60s)
Status
Standby by system
program switch
DPT1.002 X X - X -
m(≥60s)
Status
Standby
by Input H2
DPT1.002 X X - X -
m(≥60s)
Status
Normal
by Input H2
DPT1.002 X X - X -
m(≥60s)
Status
Night setback
by Input H2
DPT1.002 X X - X -
m(≥60s)
WW set temperature
Actual value
DPT9.001 X X - X -
m(≥60s)
Return temperature
Circulation
Actual value
DPT9.001 X X - X -
m(≥60s)
Pump Warm water
Off
DPT1.002 X X - X -
s(≥10s)
Pump Warm water
On
DPT1.002 X X - X -
s(≥10s)