Installation and Operating Manual
Data protocol converter Gateway WEM-KNX
8 Commissioning
83320602
▪ 1/202
1-02
▪
Ext. PHauner
31-36
8.2
Download the ETS application program
Download to the gateway
After downloading the individual address into the device, the application program with
having the configuration set can be downloaded into the device. For downloading only
the application program into the device via ETS download, the programming button does
not have to be pressed.
With the ETS it is also possible to program individual address and application program at
the same time. To do this, the programming button must be pressed.
In order to be able to use the automatic device search for storing the addresses of the
WEM system, the application program must first be loaded into the gateway.
Procedure for configuring
▶
Enter IP connection data of the system device.
▶
Start the automatic device search, after doing a first (unconfigured) application down-
load (or select the number of WEM devices and enter module addresses manually)
▶
Set the actualization rate intervals.
▶
Activate KNX group objects.
▶
Optionally, add individual descriptions to the group object names.
▶
Select the sending conditions for actualizing the active KNX group objects of the KNX
bus system.
▶
Set the sending difference for automatic sending to KNX or use the default values of
the application program.
▶
Download the completely configured application program to the gateway.