Installation and Operating Manual
Data protocol converter Gateway WEM-KNX
7 Operation
83320602
▪ 1/202
1-02
▪
Ext. PHauner
23-36
7.4.8
Communication objects for EM-HK
Object name
Object function
Data type C R W T U Actualiz.
Set Operating mode
Standby
DPT1.002 X X X X X
m(≥60s)
Set Operating mode
Time program 1
DPT1.002 X X X X X
m(≥60s)
Set Operating mode
Time program 2
DPT1.002 X X X X X
m(≥60s)
Set Operating mode
Time program 3
DPT1.002 X X X X X
m(≥60s)
Set Operating mode
Summer
DPT1.002 X X X X X
m(≥60s)
Set Operating mode
Comfort
DPT1.002 X X X X X
m(≥60s)
Set Operating mode
Normal
DPT1.002 X X X X X
m(≥60s)
Set Operating mode
Night setback
DPT1.002 X X X X X
m(≥60s)
Room set temperature Comfort
DPT9.001 X X X X X
m(≥60s)
Room set temperature Normal
DPT9.001 X X X X X
m(≥60s)
Room set temperature Night setback
DPT9.001 X X X X X
m(≥60s)
Pre-flow set
temperature
Comfort
DPT9.001 X X X X X
m(≥60s)
Pre-flow set
temperature
Normal
DPT9.001 X X X X X
m(≥60s)
Pre-flow set
temperature
Night setback
DPT9.001 X X X X X
m(≥60s)
Pre-flow set
temperature
Special level
DPT9.001 X X X X X
s(≥10s)
Su/Wi change-over
Function/Off
DPT1.002 X X X X X
m(≥60s)
Su/Wi change-over
Function/On
DPT1.002 X X X X X
m(≥60s)
Actual Operating mode System Standby
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode System Summer
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode Screed:
Function heating
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode Screed:
Laying heating
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode Holiday
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode Time program 1
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode Time program 2
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode Time program 3
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode Summer
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode Night setback
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode Normal
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode Comfort
DPT1.002 X X - X -
m(≥60s)
Actual Operating mode Standby
DPT1.002 X X - X -
m(≥60s)
Status
Room frost protection DPT1.002 X X - X -
m(≥60s)
Status
Plant frost protection DPT1.002 X X - X -
m(≥60s)
Status
Input H1: Special
DPT1.002 X X - X -
m(≥60s)
Status
Input H1: Comfort
DPT1.002 X X - X -
m(≥60s)
Status
Input H1: Normal
DPT1.002 X X - X -
m(≥60s)