4 Installation
4.1 Safety notes on installation
4.2 Delivery, transportation and storage
4.3 Preparation for assembly
Electrically isolate the plant
Prior to installation switch off the mains switch
and the safety switch.
Failure to comply could cause death or
serious injury by electric shock.
Check delivery
Check the delivery to see that it is complete and that there
has been no damage in transit. If the delivery is incomplete
or damaged, contact the deliverer.
Transport
For the burner weight see Ch. 8.7.
Storage
Be aware of the permissible ambient conditions when
storing (see Ch. 8.5).
Check burner plate
❏
The burner rating must be within the operating range of
the heating appliance. The ratings given on the burner
plate are the minimum and maximum possible firing
rates of the burner.
See capacity graphs Ch 8.2.
Space requirement
For burner dimensions see Ch. 8.6.
DANGER
4.4 Oil supply
Note:
•
Do not use cathode protection systems with steel
tanks
•
Select pipes of correct nominal bore
•
Joints must be oil tight
•
Avoid sharp bends
•
Influence of the length of the suction line
•
Pressure loss at the filter
•
Difference in height (H) between lowest oil level in the
tank and the oil pump, max 3.5 m
•
Avoid placing oil tanks outdoors and in areas subject to
frost.
With oil temperatures < 0°C, the separation of paraffin
can cause oil lines, filters and nozzles to become
blocked with wax.
•
Max. flow pressure to the pump: < 2.0 bar
•
Max. suction vacuum at the pump: < 0.4 bar
A suction vacuum > 0.4 bar can damage the
pump
•
The oil supply line must be fitted close to the burner so
that the oil hoses can be connected tension free.
•
Install oil filter before the pump. (Recommended mesh
size: 70 µm).
•
After the oil lines have been installed; carry out a
pressure test (see DIN 4755).
The burner must not be connected during the test!
ATTENTION
The operational safety of oil-fired plant is only guaranteed
when the installation of the oil supply is carried out
carefully. The plant must comply with DIN 4755 as well as
all local regulations.