background image

Installation and operating instruction
Oil burner WL10/3-D Z

9 Servicing

83292802 1/2019-04 La

42-80

9.4 Replace nozzle

Observe notes on servicing [ch. 9.1].

Do not clean nozzles, always fit new nozzles.

Place burner into service position A [ch. 9.3].
Unplug ignition cable 

4

.

Undo screw 

1

 and remove diffuser.

Counter-hold on the nozzle body 

3

 using a spanner and remove nozzle 

2

.

Fit new nozzle ensuring it is seated tightly.
Refit diffuser in reverse order.
Set nozzle distance [ch. 9.7]
Set ignition electrodes [ch. 9.5]

4

1

2

3

Summary of Contents for WL10/3-D Z

Page 1: ...Installation and operating instruction Oil burner WL10 3 D Z 83292802 1 2019 04 ...

Page 2: ...iption 8 3 1 Type key 8 3 2 Serial number 8 3 3 Function 9 3 3 1 Air supply 9 3 3 2 Oil supply 10 3 3 3 Electrical components 11 3 3 4 Program sequence 12 3 4 Technical data 14 3 4 1 Approval data 14 3 4 2 Electrical data 14 3 4 3 Ambient conditions 14 3 4 4 Fuels 14 3 4 5 Emissions 15 3 4 6 Rating 16 3 4 7 Dimensions 17 3 4 8 Weight 17 4 Installation 18 4 1 Installation conditions 18 4 2 Selectin...

Page 3: ...ng head 45 9 8 Removing the air regulator 46 9 9 Removing and refitting angle drive 47 9 10 Removing and refitting oil pump 48 9 11 Removing and refitting fan wheel 49 9 12 Remove burner motor 50 9 13 Removing and refitting oil pump filter 51 9 14 Replacing the fuse 52 10 Troubleshooting 53 10 1 Procedures for fault conditions 53 10 1 1 Illuminated push button off 53 10 1 2 Illuminated push button...

Page 4: ... carried out by personnel who have the relevant train ing and instruction Persons with limited physical sensory or mental capabilities may only work on the unit if they are supervised or have been trained by an authorised person Children must not play with the unit 1 2 Symbols DANGER Immediate danger with high risk Non observance can lead to serious injury or death WARNING Danger with medium risk ...

Page 5: ...bservance of the manual operation with faulty safety equipment continual operation despite a fault improper installation commissioning operation and service repairs which have been carried out incorrectly the use of non original Weishaupt parts force majeure unauthorised modifications made to the unit the installation of additional components which have not been tested with the unit the installati...

Page 6: ... only be used in enclosed rooms Improper use could endanger the health and safety of the user or third parties cause damage to the unit or other material assets 2 2 Safety measures Safety relevant fault conditions must be eliminated immediately Components which show increased wear and tear or whose design lifespan is or will be exceeded prior to the next service should be replaced as a precaution ...

Page 7: ...serts which hinder flame burnout Use only original Weishaupt replacement parts 2 4 Noise emission The noise emissions are determined by the acoustic behaviour of all components fitted to the combustion system Prolonged exposure to high noise levels can lead to loss of hearing Provide oper ating personnel with protective equipment Noise emissions can further be reduced with a sound attenuator 2 5 D...

Page 8: ...4 La 8 80 3 Product description 3 1 Type key WL10 3 D Z W Type W burner L Fuel Oil EL 10 Size 3 Ratings size D Construction Z Version two stage 3 2 Serial number The serial number on the name plate identifies the product This is required by Weishaupt s customer service department 1 1 Name plate Ser No ...

Page 9: ...mbustion manager drives the air damper via actuator At burner shutdown the air damper closes automatically At burner shutdown the air dampers close automatically Fan wheel The fan wheel supplies the air from the air intake housing to the combustion head Diffuser The air gap between flame tube and diffuser is adjusted by positioning the diffuser This adjusts the mixing pressure and the air quantity...

Page 10: ...pressure regulating valve keeps the oil pressure constant Solenoid valves The solenoid valves open and close the oil supply For ignition the combustion manager opens stage 1 solenoid valve Stage 2 solen oid valve opens or closes depending on heat demand Sequence diagram 1 2 4 3 1 Oil pump on burner with two solenoid valves fitted 2 Stage 1 solenoid valve normally closed 3 Nozzle head with nozzle 4...

Page 11: ...r It controls the sequence of operation and monitors the flame Burner motor The burner motor drives the fan wheel and the oil pump Ignition unit The electronic ignition unit creates a spark at the electrode which ignites the fuel air mixture Flame sensor The combustion manager monitors the flame signal via the flame sensor If the flame signal becomes too weak the combustion manager carries out a c...

Page 12: ...ses the fuel Safety time With fuel release safety time TS and post ignition time TNZ start The flame signal must be present within the safety time TS Operation The burner is in operation The combustion manager monitors the flame signal via the flame sensor Depending on the regulator demand for stage 2 stage 2 solenoid valve K13 opens or closes The residence time partial load TVK prevents cycling b...

Page 13: ...age 2 TVK Residence time partial load stage 1 min 5 s F2 Temperature or pressure limiter TV Pre purge time 16 2 s K10 Anti siphon valve optional Voltage is applied K11 Stage 1 solenoid valve Flame signal present K13 Stage 2 solenoid valve Current path M1 Burner motor START orange M20 Air damper actuator Ignition phase flashing orange P11 Control lamp operation optional Burner operation green P13 C...

Page 14: ... Consumption at start max 327 W Consumption during operation max 227 W Power consumption max 1 4 A Internal unit fuse T6 3H IEC 127 2 5 External fuse max 16 AB 3 4 3 Ambient conditions Temperature in operation 10 1 40 C Temperature during transport storage 20 70 C relative humidity max 80 no dew point 1 with the relevant suitable fuel oil and layout of oil supply 3 4 4 Fuels Fuel oil EL to DIN 516...

Page 15: ...uel combustion air temperature and humidity medium temperature Sound levels Dual number noise emission values Measured sound power level LWA re 1 pW Uncertainty value KWA 71 4 dB A 1 dB A Measured sound pressure level LpA re 20 μPa Uncertainty value KpA 65 4 dB A 2 dB A 1 Determined to ISO 9614 2 2 Determined at 1 metre distance from the front of the burner The measured noise levels plus uncertain...

Page 16: ...g for fuel oil EL Capacity graph Capacity graph to EN 267 The capacity data given relates to an installation elevation of 500 m above sea level For installation elevations above 500 m a capacity reduction of approx 1 per 100 m applies A limited capacity graph is valid for ducted air intake 0 6 0 8 0 4 0 2 0 0 2 0 4 0 6 0 8 1 0 1 2 50 45 55 60 65 70 75 80 85 90 95 100 105 4 0 4 5 5 0 5 5 6 0 6 5 7 ...

Page 17: ...La 17 80 3 4 7 Dimensions Burner weishaupt 165 mm 345 mm 1 330 mm 353 mm 108 mm 165 mm 32 mm 270 mm 1 140 mm without combustion head extension 240 mm with combustion head extension 100 mm 340 mm with combustion head extension 200 mm 440 mm with combustion head extension 300 mm 3 4 8 Weight approx 14 kg ...

Page 18: ...yond the front edge of the combustion head The refractory can take a conical shape min 60 Refractory may not be required on boilers with water cooled front unless the man ufacturer gives other instructions Following installation the aperture 4 between flame tube and refractory should be filled with flame proof resilient insulating material Do not make solid Heat exchangers with deep refractories o...

Page 19: ...d 1 10 gph 2 Only from 12 bar pump pressure and single pipe system higher oil temperat ures Pump pressure setting Stage 1 Stage 2 10 14 bar 20 22 24 bar Spray characteristic and spray angle varies depending on pump pressure Nozzle selection table Different load values are possible due to tolerances Stage 1 Burner capacity kW at pump pressure Nozzle size gph 10 bar 11 bar 12 bar 13 bar 14 bar 1 00 ...

Page 20: ... from burner housing Fit flange gasket 2 and burner flange 1 to the heat exchanger using screws 3 The aperture between combustion head and refractory should be filled with flame proof resilient insulating material do not make solid 1 3 2 It is possible to install the burner rotated by 180 if space is limited This requires conversion measures ch 4 3 1 ...

Page 21: ...g instruction Oil burner WL10 3 D Z 4 Installation 83292802 1 2019 04 La 21 80 Fit nozzle ch 9 4 Set ignition electrodes ch 9 5 Check nozzle distance and adjust if necessary ch 9 7 Mount burner with screws 1 to burner flange 1 ...

Page 22: ...ws 4 x 12 Remform shaft 58 8 mm fixing screws for actuator M4 x 30 metric pressure hose DN 4 286 mm Place stay bolt 1 into neighbouring threaded holes 1 Place burner into service position A ch 9 3 Remove actuator 6 Remove shaft 5 Fit actuator adapter 3 Fit longer shaft 4 to actuator Turn indicator 1 to CLOSED position and hold Mount actuator rotated by 180 whilst sliding the shaft 4 into the star ...

Page 23: ...t nozzle ch 9 4 Set ignition electrodes ch 9 5 Check nozzle distance and adjust if necessary ch 9 7 Rotate burner by 180 and secure with screws 3 Remove oil line 4 Undo fixing screws 2 for oil pump and rotate oil pump by 180 Tighten screws 2 Fit pressure hose 5 supplied with conversion kit fit elbow end to pump fit straight end to nozzle assembly 1 5 4 3 2 ...

Page 24: ... max 2 bar 1 Supply temperature max 60 C 1 1 Measured at the pump Check conditions for oil hoses Length 1200 mm Oil hose connection G Nominal pressure 10 bar Thermal load max 100 C Connect oil supply CAUTION Damage to the oil pump caused by incorrect connection Mixing up supply and return can damage the oil pump Ensure correct connection of oil hoses to the supply and return of the pump Fit oil ho...

Page 25: ... tension consider length of hose required for the service position do not kink oil hoses curve radius 1 of 50 mm must be maintained If these conditions for connection can not be met Adapt oil supply on site 1 Purge oil supply and ensure it is tight CAUTION Oil pump seized due to running dry Pump could be damaged Fill oil supply with oil and purge Ensure oil supply is tight ...

Page 26: ...he device from the power supply prior to starting any work Safeguard against accidental restart The electrical connection must only be carried out by qualified electricians Ob serve local regulations Observe wiring diagram ch 11 2 Check polarity and wiring of 7 pole connection plug 1 and 4 pole connection plug 2 Plug in connection plugs 1 2 With remote reset install connection line separately Do n...

Page 27: ...ss illuminated push button The illuminated push button on the combustion manager has the following func tions display operating condition ch 6 2 display fault codes ch 10 1 2 reset burner lockout ch 10 1 2 Re starting the burner during burner operation Press illuminated push button for 1 second 6 2 Display Illuminated push button Operating condition orange Start phase Flashing orange Ignition and ...

Page 28: ...ble to measure the flue gas the heat exchanger and flue gas ducting up to the test point are sound ex traneous air influences the test results the operating instructions of the heat exchanger are complied with a heat demand is available Additional system related tests could be necessary Please observe the operating guidelines for the individual components On installations with process equipment th...

Page 29: ...ply pressure Pressure gauge for pump pressure WARNING Oil leakage from oil pressure measuring devices due to constant load Oil pressure measuring devices could be damaged and cause environmental pollu tion through leakage Remove oil measuring devices once commissioning is complete Close fuel shut off devices Remove closing plug on the pump Connect vacuum gauge 1 and pressure gauge 2 1 2 ...

Page 30: ...ph Determine the diffuser setting dimension X and air damper setting required from the diagram and note down Example Burner capacity stage 2 stage 1 required 90 kW 60 kW Diffuser setting dimension X 8 8 mm Air damper setting stage 2 stage 1 59 32 Diffuser default settings 3 4 5 6 7 8 9 10 11 55 60 65 70 75 80 85 95 100 105 90 1 2 1 Combustion heat rating kW 2 Diffuser settings dimension X mm Air d...

Page 31: ...setting determined at limit switches ST2 and ST1 Set the switch point MV2 Oil to approx 1 3 of the setting movement between ST1 and ST2 MV2 Oil ST2 ST1 x 0 33 ST1 ST0 ST2 ST1 MV2 Oel ZL Gas ST0 0 ST2 ST1 MV2 Oel Determine mixing pressure Determine the mixing pressure required for the preset combustion heat rating from the diagram and note down 45 50 55 60 65 70 75 90 95 100 85 2 5 2 0 3 0 3 5 4 0 ...

Page 32: ...can be used to switch the stages during commissioning Order No 130 103 15 012 Heat demand from the boiler controller required Open fuel shut off devices Unplug 4 pole connection plug Switch on voltage supply Illuminated push button lights up red Press illuminated push button for 1 second Burner starts in accordance with the program sequence and stops at stage 1 ch 3 3 4 Set pump pressure for stage...

Page 33: ...r setting has to be adjusted The air damper setting for stage 2 must be adjusted in stage 1 Check combustion values Determine combustion limit ch 7 4 Set excess air using air damper setting limit switch ST2 and diffuser setting whilst observing the mixing pressure determined ch 7 1 2 3 Adjust stage 1 Exit this stage if the air damper setting has to be adjusted The air damper setting for stage 1 mu...

Page 34: ...between ST1 and ST2 MV2 Oil ST2 ST1 x 0 33 ST1 5 Check start behaviour and switch point Switch off burner Plug in 4 pole connection plug Re start the burner Check start behaviour Check stage 2 switch excess air phase CO content prior to switch over must not be too long flame must not fail If necessary correct settings If the existing settings have been changed Re check start behaviour and switch p...

Page 35: ... devices once commissioning is complete If necessary replace plug switch with 4 pole connection plug Check control and safety devices Check tightness of oil carrying components Enter combustion values and settings in the commissioning record and or test sheet Mount cover on burner Inform the operator about the use of the equipment Hand the installation and operating manual to the operator and info...

Page 36: ...e gas temperature Check flue gas temperature Ensure that the flue gas temperature complies with the data provided by the boiler manufacturer If necessary adjust flue gas temperature e g Increase burner capacity in partial load to avoid condensation in the flue gas ducts except on condensing units Reduce burner capacity in full load to improve efficiency Adjust heat exchanger to the data provided b...

Page 37: ...Installation and operating instruction Oil burner WL10 3 D Z 8 Shutdown 83292802 1 2019 04 La 37 80 8 Shutdown For breaks in operation Switch off burner Close fuel shut off devices ...

Page 38: ...s more frequent checks may be required Components which show increased wear and tear or whose design lifespan is or will be exceeded prior to the next service should be replaced as a precaution The design lifespan of the components is listed in the service plan ch 9 2 Weishaupt recommends a service contract is entered into to ensure regular in spections The following components must only be replac...

Page 39: ...e can lead to electric shock Do not touch ignition device during the ignition process Check tightness of oil carrying components Check function of ignition flame monitoring oil pump pump pressure and suction resistance control and safety devices Check combustion values if necessary re adjust the burner Enter combustion values and settings in the commissioning record Refit cover ...

Page 40: ...ears 2 Replace Flame sensor Soiling Clean Damage 250 000 burner starts or 10 years 2 Replace Flame tube diffuser Soiling Clean Damage Replace Oil nozzle Soiling wear Replace Recommendation at least every 2 years Oil pump filter Soiling Replace Oil hose Damage oil escaping Replace Recommendation every 5 years Oil solenoid valve Soundness 250 000 burner starts or 10 years 2 Replace oil pump 1 The sp...

Page 41: ...04 La 41 80 9 3 Service position Observe notes on servicing ch 9 1 Remove bolts 1 If necessary remove oil hoses If the burner is placed into service position B If necessary unplug actuator plug Place the burner into the required service position Service position A A 1 Service position B B 1 ...

Page 42: ...o not clean nozzles always fit new nozzles Place burner into service position A ch 9 3 Unplug ignition cable 4 Undo screw 1 and remove diffuser Counter hold on the nozzle body 3 using a spanner and remove nozzle 2 Fit new nozzle ensuring it is seated tightly Refit diffuser in reverse order Set nozzle distance ch 9 7 Set ignition electrodes ch 9 5 4 1 2 3 ...

Page 43: ... 5 Set ignition electrodes Observe notes on servicing ch 9 1 The ignition electrodes must not touch the nozzle s atomising cone Place burner into service position A ch 9 3 Check distance of ignition electrodes If necessary adjust ignition electrodes by slightly bending 2 0 2 5 mm 1 0 2 0 mm 1 5 2 0 m m ...

Page 44: ...10 3 D Z 9 Servicing 83292802 1 2019 04 La 44 80 9 6 Removing the mixing head Observe notes on servicing ch 9 1 Unplug ignition cable 1 Remove oil line 3 Remove flame sensor 4 Undo screws 2 Turn mixing head to the left up to the recess and remove 4 3 1 2 ...

Page 45: ...e tighten screw 1 2 1 A 5 mm Check basic setting Dimension S1 can only be checked when the burner is mounted to a boiler door which is hinged open Hinge open boiler door or if necessary remove mixing head ch 9 6 Turn setting screw 1 until the indicating bolt 2 is flush with the nozzle as sembly cover dimension X 0 mm Check dimension S1 and or dimension Lx Set dimension S1 and or dimension Lx using...

Page 46: ...Z 9 Servicing 83292802 1 2019 04 La 46 80 9 8 Removing the air regulator Observe notes on servicing ch 9 1 Remove actuator plug 5 Place burner into service position A ch 9 3 Remove bolts 1 Remove intake housing 3 Remove bolts 4 Remove air regulator 2 4 5 1 2 3 ...

Page 47: ... caused by turning the hub Actuator could be damaged Do not turn hub manually or with tool Remove intake housing ch 9 8 Open air damper 6 until position 7 has been reached and hold tight Fit angle drive to shaft Secure angle drive Mount intake housing ch 9 8 Fit frame 4 Fit shaft 8 to actuator For installation the actuator should be set to 0 Turn indicator 1 to CLOSED position and hold Place actua...

Page 48: ... Remove oil hoses 5 Remove oil line 4 Undo screws 2 and remove oil pump Refitting Install oil pump in reverse order and ensure correct alignment of coupling 3 ensure correct allocation of flow and return of the oil hoses CAUTION Damage to the oil pump caused by incorrect connection Mixing up supply and return can damage the oil pump Ensure correct connection of oil hoses to the supply and return o...

Page 49: ...efitting fan wheel Observe notes on servicing ch 9 1 Removing Place housing cover into service position B ch 9 3 Remove grub screw 1 and remove fan wheel Refitting Refit fan wheel in reverse order and ensure correct alignment on the motor shaft 2 screw in new grub screw 1 turn fan wheel to ensure it moves freely 2 1 1 2 ...

Page 50: ...n Oil burner WL10 3 D Z 9 Servicing 83292802 1 2019 04 La 50 80 9 12 Remove burner motor Observe notes on servicing ch 9 1 Remove the oil pump ch 9 10 Remove fan wheel ch 9 11 Unplug plug 1 Hold motor and remove screws 2 Remove motor 3 1 2 ...

Page 51: ...02 1 2019 04 La 51 80 9 13 Removing and refitting oil pump filter Observe notes on servicing ch 9 1 Removing Close fuel shut off devices Remove bolts 1 Remove pump cover Replace filter 3 and gasket 2 2 3 1 Refitting Refit filter in reverse order ensuring sealing surfaces are clean ...

Page 52: ...WL10 3 D Z 9 Servicing 83292802 1 2019 04 La 52 80 9 14 Replacing the fuse Observe notes on servicing ch 9 1 Remove all plugs from the combustion manager Remove screws from the combustion manager Remove combustion manager Replace fuse T6 3H IEC 127 2 5 ...

Page 53: ...ating External fuse has tripped 1 Check fuse Heating switch is set to Off Switch on heating switch Temperature limiter or pressure limiter on heat exchanger has triggered 1 Reset temperature limiter or pressure limiter on heat exchanger Low water safety interlock on heat ex changer has triggered 1 Top up water Reset low water safety interlock on heat exchanger Temperature regulator or pressure reg...

Page 54: ...d read Press illuminated push button for 5 seconds Illuminated push button briefly lights up orange Illuminated push button flashes red Count between the flashing pauses and flashing signals and note down Rectify cause of fault see table Resetting WARNING Damage resulting from incorrect fault repair Incorrect fault repair can cause damage to the equipment and injure personnel Do not carry out more...

Page 55: ... does not detect a flame signal Flame sensor soiled Clean flame sensor Flame sensor defective Replace flame sensor Illumination insufficient Check burner setting Burner motor does not run Oil pump seized Replace oil pump ch 9 10 Capacitor defective Replace capacitor Burner motor defective Replace burner motor ch 9 12 No flame formation despite ignition and oil supply Nozzle distance incorrect Chec...

Page 56: ...defective Check flame sensor if necessary replace Flashing 8 times Release contact fault Contact X3 12 not closed Bridging plug No 12 is missing Plug in bridging plug No 12 Flashing 9 times Flame failure during opera tion stage 2 Flame has failed Oil supply leaking Check oil supply Vacuum too high Oil nozzle soiled Replace oil nozzle ch 9 4 Flame signal insufficient Burner setting incorrect Check ...

Page 57: ...o heat demand Find and eliminate extraneous light source Flashing red orange with pause Excess voltage Check voltage supply Flashing orange red Low voltage Check voltage supply Internal unit fuse F7 faulty Replace fuse ch 9 14 Combustion manager fault Replace combustion manager Flashing green Flame sensor soiled Clean flame sensor Flame sensor defective Replace flame sensor Burner operation with w...

Page 58: ...e worn Flame tube diffuser has heavy soot deposit Oil nozzle defective Replace nozzle Mixing head set incorrectly Set mixing head ch 9 7 Incorrect combustion air quantity Adjust burner Boiler room ventilated insufficient Ensure sufficient boiler room ventila tion Wrong oil nozzle Check nozzle type Nozzle distance incorrect Check nozzle distance adjust if necessary ch 9 7 Combustion pulsating or bu...

Page 59: ...n 83292802 1 2019 04 La 59 80 11 Technical documentation 11 1 Conversion table unit of pressure Bar Pascal Pa hPa kPa MPa 0 1 mbar 10 0 1 0 01 0 00001 1 mbar 100 1 0 1 0 0001 10 mbar 1 000 10 1 0 001 100 mbar 10 000 100 10 0 01 1 bar 100 000 1 000 100 0 1 10 bar 1 000 000 10 000 1 000 1 ...

Page 60: ...X4 1 M M20 X5 1 S3 4 F1 P13 W FM 10 K1 K3 5 1 4 6 11 3 12 13 X6 X7 X4 1 X3 F7 W FM 10 X5 1 B15 Temperature or pressure regulator B16 Temperature or pressure regulator stage 2 F1 External fuse F2 Temperature or pressure limiter F7 Internal unit fuse T6 3H IEC 127 2 5 M20 Air damper actuator P11 Control lamp operation optional P13 Control lamp operation stage 2 optional P6 Control lamp lockout optio...

Page 61: ...3292802 1 2019 04 La 61 80 X3 3 C1 M1 M X3 12 X3 1 X3 6 X3 5 X3 4 X3 13 T1 B1 K11 K13 K10 h P11 1 K2 K3 K5 K4 B1 Flame sensor C1 Motor capacitor K10 Anti siphon valve optional K11 Stage 1 solenoid valve K13 Stage 2 solenoid valve M1 Burner motor P11 1 Hours counter optional T1 Ignition unit ...

Page 62: ... way that the oil hoses can be con nected free of tension Fit oil filter in front of pump recommended mesh aperture 70 μm Suction resistance and supply pressure CAUTION Pump damage due to excessive suction resistance A suction resistance greater than 0 4 bar can damage the pump Reduce suction resistance or install oil supply pump or suction unit whilst observing the maximum supply pressure at the ...

Page 63: ...phon valve on single pipe system max 8 m between anti siphon valve and automatic de aer ator on two pipe system max 20 m between anti siphon valve and oil pump max 8 m max 4 6 m max 20 m max 4 6 m 1 1 Single pipe system CAUTION Damage to the oil pump caused by incorrect connection Mixing up supply and return can damage the oil pump Ensure correct connection of oil hoses to the supply and return of...

Page 64: ...perating instruction Oil burner WL10 3 D Z 13 Spares 83292802 1 2019 04 La 64 80 13 Spares 1 17 1 01 1 02 1 03 1 20 1 19 1 05 1 11 1 09 1 15 1 08 1 07 1 06 1 21 1 20 1 18 1 22 1 17 1 12 1 14 1 13 1 14 1 13 1 10 1 04 1 16 ...

Page 65: ...n cable 241 200 01 247 1 11 Grommet for oil hose 241 400 01 177 1 12 Housing cover 241 110 01 317 1 13 Screw G1 8A DIN 908 409 004 1 14 Sealing ring 10 x 13 5 x 1 5 EN 1514 441 033 1 15 Bracket for oil hose and cable 241 400 01 367 1 16 Stay bolt cover 241 210 01 207 1 17 Screw M6 burner housing 241 110 01 297 1 18 Burner flange 241 110 01 05 7 Screw M8 x 30 DIN 912 402 517 Washer 8 4 DIN 433 430 ...

Page 66: ...Installation and operating instruction Oil burner WL10 3 D Z 13 Spares 83292802 1 2019 04 La 66 80 2 06 2 08 2 05 2 01 2 11 2 16 2 17 2 12 2 18 2 02 2 14 2 13 2 07 2 04 2 03 2 09 2 10 2 15 ...

Page 67: ...aring for air damper shaft 241 110 02 107 2 09 Shaft air damper angle drive 241 210 02 057 2 10 Angle drive spring 2 241 110 02 062 2 11 Screw 4 x 12 Torx Plus Remform 409 320 2 12 Shaft angle drive actuator 241 400 02 157 2 13 Frame for actuator 241 210 02 037 2 14 Screw 4 x 30 Torx Plus Delta PT 409 325 2 15 Actuator STD 4 5 24V B0 36 6 4NL 651 102 2 16 Screw 4 x 35 Combi Torx Plus Remform 409 3...

Page 68: ...Installation and operating instruction Oil burner WL10 3 D Z 13 Spares 83292802 1 2019 04 La 68 80 3 08 3 05 3 08 3 07 3 03 3 04 3 01 3 02 3 06 ...

Page 69: ...07 3 02 Solenoid coil T80 Suntec 220 240V 50 60Hz 604 495 3 03 Plug coupling for motor 652 135 3 04 Oil line pump nozzle assembly 241 110 06 018 3 05 Screwed union 24 SX LL04 ST 452 020 3 06 Pressure hose DN 4 286 mm for installation rotated by 180 491 246 3 07 Bypass plug BUZ 06 LL with nut 241 100 06 012 3 08 Oil hose DN 4 1200 mm Standard 491 126 diffusion resistant 491 131 ...

Page 70: ...perating instruction Oil burner WL10 3 D Z 13 Spares 83292802 1 2019 04 La 70 80 4 10 4 12 4 09 4 24 4 01 4 25 4 17 4 14 4 13 4 07 4 08 4 23 4 22 4 21 4 15 4 05 4 06 4 11 4 02 4 03 4 27 4 04 4 18 4 19 4 20 4 26 4 17 4 16 ...

Page 71: ...77 4 08 Adjusting screw M6 x 88 241 400 10 097 4 09 Flange AGK42 QRB4 600 682 4 10 Screw 4 x 12 Torx Plus 20IP 409 320 4 11 Strap AKG43 for QRB4 600 681 4 12 Flame sensor QRB4B 241 050 12 072 4 13 Plug 5 25 241 110 10 087 4 14 Indicating bolt M6 x 90 241 110 10 097 4 15 Adjusting lever bottom part 241 110 10 067 4 16 Adjusting lever top part 241 110 10 077 4 17 Screw M4 x 12 Torx Plus 20IP 409 237...

Page 72: ...perating instruction Oil burner WL10 3 D Z 13 Spares 83292802 1 2019 04 La 72 80 4 10 4 12 4 09 4 24 4 01 4 25 4 17 4 14 4 13 4 07 4 08 4 23 4 22 4 21 4 15 4 05 4 06 4 11 4 02 4 03 4 27 4 04 4 18 4 19 4 20 4 26 4 17 4 16 ...

Page 73: ...en 612 212 1 00 gph 60 H Steinen 612 517 1 10 gph 60 H Steinen 612 518 1 25 gph 60 H Steinen 612 519 1 35 gph 60 H Steinen 612 520 1 50 gph 60 H Steinen 612 521 1 00 gph 45 SF Fluidics 602 062 1 10 gph 45 SF Fluidics 602 063 1 25 gph 45 SF Fluidics 602 064 1 35 gph 45 SF Fluidics 602 065 1 50 gph 45 SF Fluidics 602 066 1 00 gph 45 HF Fluidics 602 710 1 10 gph 45 HF Fluidics 602 711 1 25 gph 45 HF ...

Page 74: ...Installation and operating instruction Oil burner WL10 3 D Z 13 Spares 83292802 1 2019 04 La 74 80 5 01 5 04 5 08 5 10 5 09 5 12 5 13 5 06 5 07 5 05 5 11 5 03 5 02 5 10 ...

Page 75: ...utton extension AGK20 19 600 357 5 04 Cover clip AGK63 600 312 5 05 Bridging plug No 12 3 pole 241 050 12 032 5 06 Plug unit ST18 7 716 549 5 07 Plug unit ST18 4 716 546 5 08 Plug in switch ST18 4 version Z 130 103 15 012 5 09 Ignition unit type W ZG01V 230 V 100 VA 603 221 5 10 Screw M4 x 42 Combi Torx Plus 20IP 409 260 5 11 Plug cable No 3 motor 241 050 12 062 5 12 Plug cable No 5 stage 1 soleno...

Page 76: ...Installation and operating instruction Oil burner WL10 3 D Z 14 Notes 83292802 1 2019 04 La 76 80 14 Notes ...

Page 77: ...Diffuser setting 30 Dimensions 17 Display 27 Disposal 7 Drilling diagram 18 Ducted air intake 6 16 E Electrical connection 26 Electrical data 14 Electrodes 43 Emission 15 Emission class 15 Error code 54 Error codes 55 57 Errors 55 Excess air 36 Extraneous light 28 F Fabrication number 8 Fan motor 50 Fan pressure 28 31 Fan wheel 9 49 Fault 53 58 Fault history 54 Faults 57 Filter 51 62 Flame sensor ...

Page 78: ...p filter 51 Pump pressure 19 29 32 33 R Recommended nozzles 19 Refractory 18 Remote reset 26 Reset 54 Reset button 27 Residence time 13 Return 24 Ring main operation 63 S Safety measures 6 Safety time 12 13 Sequence diagram 10 12 Serial number 8 Service 38 Service contract 38 Service interval 38 Service plan 40 Service position 41 Setting dimension 45 Setting gauge 45 Setting screw 45 Shutdown 37 ...

Page 79: ...83292802 1 2019 04 La ...

Page 80: ...Weishaupt GmbH 88475 Schwendi Weishaupt close by Addresses telephone numbers etc can be found at www weishaupt de We reserve the right to make changes All rights reserved Water heaters Energy storage The diverse program of potable water and energy storage for various heat sources includes storage volumes of 70 to 3 000 litres In order to minimize storage losses potable water cylinders from 140 to ...

Reviews: