Installation and operating instruction
Oil burner WL20/1-C Z
10 Troubleshooting
83307602 1/2019-04 La
60-84
The following faults must only be rectified by qualified personnel:
Fault codes
Fault
Cause
Rectification
Flashing 7 times
Flame failure during opera-
tion (stage 1)
Flame has failed
Oil supply leaking
Check oil supply
Suction resistance in front
of pump too high
Oil nozzle soiled
Replace oil nozzle
Flame signal insufficient
Burner setting incorrect
Check burner setting
Check flame signal
[ch. 7.1.1]
Flame sensor soiled
Clean flame sensor
Flame sensor defective
Check flame sensor, if
necessary replace
Flashing 8 times
Release contact fault
Contact X3:12 not closed
Bridging plug No. 12 is
missing
Plug in bridging plug No.
12
Flashing 9 times
Flame failure during opera-
tion (stage 2)
Flame has failed
Oil supply leaking
Check oil supply
Vacuum too high
Oil nozzle soiled
Flame signal insufficient
Burner setting incorrect
Check burner setting
Check flame signal
[ch. 7.1.1]
Flame sensor soiled
Clean flame sensor
Flame sensor defective
Check flame sensor, if
necessary replace
Flashing 10 times
Combustion manager fault
Burner does not start
Parameters have been
changed
Combustion manager de-
fective
Reset burner [ch. 10.1.2],
if fault reoccurs replace
combustion manager