Installation and operating instruction
Oil burner WL40/1-A Z-1LN-A
4 Installation
83319702 1/2020-10 La
23-116
Nozzle selection table
Different load values are possible due to tolerances.
Stage 1
Burner capacity [kW] at pump pressure
Nozzle size [gph]
9 bar
10 bar
11 bar
12 bar
3.00
–
–
143
149
3.50
149
158
165
174
4.00
171
181
189
199
4.50
192
204
213
223
5.00
213
226
237
248
5.50
235
249
261
273
6.00
257
271
284
298
6.50
278
291
308
321
7.00
299
317
332
346
7.50
320
338
355
370
8.00
343
361
380
395
Stage 2
Burner capacity [kW] at pump pressure
Nozzle size [gph]
17 bar
18 bar
20 bar
22 bar
3.00
176
181
192
201
3.50
206
211
224
234
4.00
235
241
256
267
4.50
264
271
287
301
5.00
293
301
320
336
5.50
322
331
351
368
6.00
351
361
382
401
6.50
380
393
415
435
7.00
411
421
448
468
7.50
440
452
479
501
8.00
470
485
514
–
Conversion of burner capacity to oil throughput see formula below.
Oil throughput in kg/h =
Burner capacity in kW
11.9 kWh/kg