Installation and operating instruction
Oil burner WL40/1-A Z-1LN-A
3 Product description
83319702 1/2020-10 La
15-116
B4
P11P13
W-FM 25
B5
P
P
B15
L
T1 T2
F2
N
L N
K11
5
K14
1
K13
6
M
M20
T1
4
B1
13
M
1
M1
3
T
I
T
V
T
N
T
S
P
B16
T8
T6
T7
1234
5
B1
Flame sensor
1
Operating point P
0
(ignition position)
B15
Temperature or pressure regulator
2
Operating point P
1
(stage 1)
B16
Temperature or pressure regulator stage 2
3
Operating point P
2
(solenoid valve stage 2)
F2
Temperature or pressure limiter
4
Operating point P
9
(stage 2)
K11
Stage 1 solenoid valve
5
Operating phase
K13
Stage 2 solenoid valve
T
I
Initialisation time (Test): 3 s
K14
Safety solenoid valve
T
N
Post-purge time: 2 s [ch. 6.2.3]
M1
Burner motor
T
S
Safety time: 3 s
M20
Air damper actuator
T
V
Pre-purge time: 20 s
P11
Control lamp operation (optional)
Voltage is applied
P13
Control lamp stage 2 (optional)
Flame signal present
T1
Ignition unit
Current path