3.4 Technical data
3.4.1 Approval data
DIN CERTCO
5G820
Basic standards
EN 267:2011
Additional standards, see EU conformity certifica-
tion.
3.4.2 Electrical data
Mains voltage / mains frequency
230 V/50 Hz
Consumption at start
max 901 W
Consumption during operation
max 801 W
Power consumption
max 4.0 A
Internal unit fuse
T6.3H, IEC 127-2/5
External fuse
max 16 AB
3.4.3 Ambient conditions
Temperature in operation
–10
(1
… +40 °C
Temperature during transport / storage
–20 … +70 °C
relative humidity
max 80 %, no dew point
Installation elevation
max 2000 m
(2
(1
With the relevant suitable fuel oil and layout of oil supply.
(2
Consultation with Weishaupt is required for higher installation elevation.
3.4.4 Fuels
Fuel oil EL to DIN 51603-1
Fuel oil EL A Bio 10 to DIN 51603-6
Fuel oil EL to ÖNORM-C1109 (Austria)