Installation and operating instruction
Oil burner WL40/1-A Z-1LN-A
3 Product description
83319702 1/2020-10 La
18-116
3.4.5 Emissions
Flue gas
To EN 267 the burner complies with emission class 3.
The NO
x
values are influenced by:
combustion chamber dimensions
flue gas system
fuel
combustion air (temperature and humidity)
medium temperature
Combustion chamber dimensions, see Weishaupt Partner Portal / Documents and
Applications / Online Applications / NO
X
calculation for burners.
Sound levels
Dual number noise emission values
Measured sound power level L
WA
(re 1 pW)
Uncertainty value K
WA
78
4
dB(A)
(1
dB(A)
Measured sound pressure level L
pA
(re 20 μPa)
Uncertainty value K
pA
73
4
dB(A)
(2
dB(A)
(1
Determined to ISO 9614-2.
(2
Determined at 1 metre distance from the front of the burner.
The measured noise levels plus uncertainty values form the upper limit value, which