Installation and operating instruction
Oil burner WL40Z-A 1LN
7 Commissioning
83298902 2/2019-05 La
38-112
7.1.3 Setting values
Set mixing head relative to the combustion heat rating required. For this, the dif-
fuser setting and the air damper setting should be matched.
Determine diffuser setting and air damper setting
Do not operate the burner outside of the capacity graph.
Determine the diffuser setting (dimension X) and air damper setting required
from the diagram and note down.
Example
Burner capacity stage 2 / stage 1 required
335 kW / 226 kW
Diffuser setting (dimension X)
13.8 mm
Air damper setting stage 2 / stage 1
57° / 32°
Diffuser default settings
100
360
380
340
320
300
280
260
240
220
200
180
160
140
120
4
6
8
10
12
14
16
2
1
1
Combustion heat rating [kW]
2
Diffuser settings (dimension X) [mm]
Air damper default settings
100
360
380
340
320
300
280
260
240
220
200
180
160
140
120
10
20
30
40
50
60
2
1
3
4
1
Combustion heat rating [kW]
3
Stage 1
2
Air damper setting [°]
4
Stage 2