Installation and operating instruction
Oil burner WL5/1-B H-2LN
4 Installation
83058402 1/2019-04 La
18-72
4 Installation
4.1 Installation conditions
Burner type and capacity graph
Burner and heat exchanger must be matched.
Check burner type and burner capacity.
Installation location
Prior to installation ensure that:
sufficient space is available for normal and service position [ch. 3.4.7],
sufficient combustion air is available, if necessary install ducted air intake,
Prepare heat exchanger
The refractory
3
must not protrude beyond the recirculation aperture
5
. It can,
however, take a conical shape (min 60°).
Refractory may not be required on boilers with water-cooled front, unless the man-
ufacturer gives other instructions.
Following installation, the aperture
4
between flame tube and refractory should be
filled with flame-proof, resilient insulating material. Do not make solid.
45°
130 ... 150 mm
M8
110 mm
60°
120 mm
100 mm
80 mm
206 ... 231 mm
135 mm
1
2
3
4
5
1
Boiler plate
2
Flange gasket
3
Refractory
4
Aperture
5
Recirculation aperture