Installation and operating instruction
Oil burner WL5/1-B
7 Commissioning
83272002 1/2019-04 La
29-76
Set diffuser
With dimension X = 0 mm the indicating bolt is flush with the cover of the nozzle
assembly.
Turn screw
1
, until dimension X equals the value determined.
X
1
Set air damper
Turn setting screw
1
until the scale shows the value determined.
A
B
1
1
A Manual adjustment
B Actuator (optional)
Determine mixing pressure
Determine the mixing pressure required for the preset combustion heat rating
from the diagram and note down.
20
22
24
26
28
30
32
34
36
38
40
42
2.7
2.8
2.9
3.0
3.1
3.2
3.3
3.4
3.5
3.6
2
1
1
Combustion heat rating [kW]
2
Mixing pressure [mbar]
Guide values, which may vary depending on combustion chamber resist-
ance.