Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
4 Installation
83252902 1/2019-09 La
25-84
3. Set distance flame tube to diffuser
The distance flame tube to diffuser (dimension S1) determined from the setting dia-
gram is set at setting bolt
1
using auxiliary dimension E
V
.
Measure auxiliary dimension E
V
and compare to the table below.
Distance determined
Flame tube to diffuser (dimension S1)
Auxiliary dimension E
v
123 mm
30 mm (combustion head CLOSED)
118 mm
25 mm
113 mm
20 mm
108 mm
15 mm
103 mm
10 mm (combustion head OPEN)
If auxiliary dimensions E
V
varies from the measured value by more than 5 mm:
Undo locknut on setting bolt
1
.
Turn setting bolt until auxiliary dimension E
V
has been reached.
Re-tighten locknut.
1
S1
Ev