Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
9 Servicing
83252902 1/2019-09 La
49-84
9.4 Set ignition electrodes
Observe notes on servicing [ch. 9.1].
The distance between the ignition electrodes and other components must be
greater than the spark gap between the electrodes.
The ignition electrodes must not touch the nozzle's atomising cone.
Hinge open the burner [ch. 9.3].
Remove nozzle assembly (only with combustion head extension).
Undo screw
1
on the ignition electrode holder.
Set ignition electrodes.
Tighten screw.
3 ... 4 mm
4 ... 6 mm
1