background image

14 

Part Number: 9294045C  03/22

Operation 

Section 3

FREEZERS

Plug the unit in to begin operation. At initial start-up or 

anytime power is disconnected, then reconnected to the 

unit, the control will start the unit in defrost.
The unit can be turned on and off by pressing the on/off 

button on control. The unit will begin in a defrost cycle if it 

is turned on at the control. 
After initializing, the control will immediately enter a 

DEFROST mode. The compressor and condenser fan as well 

as the evaporator fan will remain off until initial defrost 

is complete. This initial defrost cycle may take up to 15 

minutes to complete, then the freezing cycle will begin. 
After initializing and the defrost cycle, the electronic 

temperature control will cycle the compressor, evaporator 

fan motor, and condenser fan motor to maintain box 

temperature at the control setting.
With the doors closed, the temperature of the cabinet 

should reach 0°F (-18°C) on freezers in about one hour 

after the freezing cycle begins. The electronic temperature 

control constantly monitors box temperature as well as 

evaporator coil temperature to maintain consistent product 

temperatures. As an added energy-saving feature, the 

electronic controller will switch the evaporator fan motor 

on and off with the compressor and condenser fan motor.

During normal operation the evaporator fan may cycle 

and/or pulse independently of the compressor. Consult 

the service manual or contact Technical Support at 

1-844-724-CARE if you are unsure of the proper 

function.

Electronic Temperature Control Location & Adjustment

The control is located in the control box at the rear of the 

unit. It is factory set at mid-range to maintain about -3°F 

(-18°C) box temperature. To adjust for colder temperatures, 

press and hold the set button until the current set point 

appears and is blinking on the screen.  Press the down 

arrow to adjust to the desired temperature.  Press the set 

button to save the temperature.  
To adjust for warmer temperatures, press and hold the set 

button until the current set point appears and is blinking 

on the screen.  Press the up arrow to adjust to the desired 

temperature.  Press the set button to save the temperature 

Freezer Automatic Defrost

The control is set to defrost every 5 hours. The maximum 

defrost duration is 35 minutes. 

Freezer Manual Defrost

If a manual defrost is desired, simply unplug the unit for 

several seconds, then plug unit back in. This will cause the 

control to re-initialize and then enter a defrost cycle. The 

unit can also be put into a manual defrost by pressing and 

holding the snowflake button on the control. 
When the control enters the defrost mode, whether manual 

or automatic, it switches on the compressor and condenser 

fan motor, and energizes the hot gas solenoid to warm the 

evaporator coil and melt all frost accumulated during the 

previous refrigeration cycle. The control will continue the 

defrost cycle for a MAXIMUM of 35 minutes depending on 

the amount of frost accumulated on the evaporator coil.
After the defrost cycle is complete, the control returns 

to a normal refrigeration cycle, however the evaporator 

fan motor will not switch on for two minutes AFTER 

the compressor and condenser fan motor have begun 

operating. 

EVAPORATOR FAN OPERATION

Cooling Cycle

Defrost Cycle

Compressor 

On

Compressor 

Off

Compressor 

Off  Refrig. / 

On Freezer

Evap Fan

Evap Fan

Evap Fan

R290 

Refrigerators

On

On

On

R290 Freezer

On

Off

Off

Summary of Contents for Delfield 4000P Series

Page 1: ...d Maintenance Manual This manual is updated as new information and models are released Visit our website for the latest manual Note additional shelves shown above Part Number 9294045C 03 22 Original Document Caution Read this instruction before operating this equipment Fresh Solutions Fit For You ...

Page 2: ...wool or ceramic fibers crystalline silica and or carbon monoxide Inhalation of airborne particles of glasswool or ceramic fibers is known to the State of California to cause cancer Inhalation of carbon monoxide is known to the State of California to cause birth defects or other reproductive harm nWarning Do not use electrical appliances inside the food storage compartments of the appliance unless ...

Page 3: ...e Power Cord Chart 7 Refrigeration 8 Drain Connections 8 Caster Or Leg Installation 8 Leg Leveling 9 Caster and Leg Mounting Detail 9 Loosen Freezer Compressor Bolts 9 Section 3 Operation Controls Programming Settings 13 R290 Refrigerators 13 Freezers 14 Evaporator Fan Operation 14 Section 4 Maintenance Interior Cleaning 16 Preventing Blower Coil Corrosion 16 Exterior Cleaning 16 Drain 16 Cleaning...

Page 4: ...counter Refrigerator With Subtop And 3 75 Casters 406CA CE Undercounter Freezer Base With Stainless Steel Top 407P CE1 407P CE2 407P DHL CE1 407P DHL CE2 Undercounter Freezer Base With Stainless Steel Top 407 CE Undercounter Freezer With Subtop And 3 75 Casters 407CAP CE 407CA CE Serial Number Location The serial number on 400 series compact refrigerators and freezers is printed on the right side ...

Page 5: ... is intended for indoor use only Do not install or operate this equipment in outdoor areas Caution Do not position the air intake vent near steam or heat exhaust of another appliance The location selected for the equipment must meet the following criteria If any of these criteria are not met select another location Units are intended for indoor use only The location MUST be level stable and capabl...

Page 6: ...he vents clean and free of obstruction Legs or casters must be used and not removed Dimensions Model Length Depth Height 402P 27 69cm 28 5 72cm 39 5 100cm 403P 27 69cm 28 5 72cm 35 5 90cm 406P 27 69cm 28 5 72cm 35 5 90cm 406CAP 27 69cm 27 75 70cm 33 25 84cm 407P 27 69cm 28 5 72cm 35 5 90cm 407CAP 27 69cm 27 75 70cm 33 25 84cm ST4048P 48 122cm 28 5 72cm 39 5 100cm UC4048P 48 122cm 28 5 72cm 35 5 90...

Page 7: ...re start up GROUND FAULT CIRCUIT INTERRUPTER Ground Fault Circuit Interrupter GFCI GFI protection is a system that shuts down the electric circuit opens it when it senses an unexpected loss of power presumably to ground Welbilt does not recommend the use of GFCI GFI circuit protection to energize our equipment If code requires the use of a GFCI GFI then you must follow the local code The circuit m...

Page 8: ...or casters must be installed and the legs or casters must be screwed in completely to prevent bending When casters are installed the mass of this unit will allow it to move uncontrolled on an inclined surface These units must be tethered secured to comply with all applicable codes nWarning The unit must be installed in a stable condition with the front wheels locked Locking the front casters after...

Page 9: ... door remain closed CASTER AND LEG MOUNTING DETAIL A universal bolt hole pattern is provided on the bottom of the cabinet It will accommodate any leg or caster Simply line up the plate holes with the corresponding cabinet holes 3 40 86mm 2 82 72mm 1 75 44mm 2 14 54mm 0 94 24mm NOTE If hole pattern on caster leg matches the one above mount in middle set of holes 3 Caster 3234024 5 Caster 3234161 6 ...

Page 10: ...10 Part Number 9294045C 03 22 Installation Section 2 THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 11: ...Part Number 9294045C 03 22 11 Section 2 Installation THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 12: ...t nWarning The operator of this equipment is solely responsible for ensuring safe holding temperature levels for all food items Failure to do so could result in unsafe food products for customers nWarning Overloading shelves can damage equipment or cause bodily injury nWarning Damp or wet hands may stick to cold surfaces nWarning Do not block the supply and return air grills or the air space aroun...

Page 13: ...ion that is being delayed by a timer external signal or disabled by another process that is already going on For example the compressor icon will flash if the cabinet temperature is above the cut in temperature but the control hasn t met the minimum compressor off time E0 Air probe error E1 Coil probe error LO Low temperature alarm 20 F for 90 minutes HI High temperature alarm 20 F for 90 minutes ...

Page 14: ...box at the rear of the unit It is factory set at mid range to maintain about 3 F 18 C box temperature To adjust for colder temperatures press and hold the set button until the current set point appears and is blinking on the screen Press the down arrow to adjust to the desired temperature Press the set button to save the temperature To adjust for warmer temperatures press and hold the set button u...

Page 15: ...rning When cleaning interior and exterior of unit care should be taken to avoid the front power switch and the rear power cord Keep water and or cleaning solutions away from these parts nWarning Never use a high pressure water jet for cleaning or hose down or flood interior or exterior of units with water Do not use power cleaning equipment steel wool scrapers or wire brushes on stainless steel or...

Page 16: ...ch drain can become loose or disconnected during normal use If you notice water accumulation on the inside of the unit be sure the drain tube is connected to the evaporator drain pan If water is collecting underneath the unit make sure the end of the drain tube is in the condensate evaporator The leveling of the unit is important as the units are designed to drain properly when level Be sure all d...

Page 17: ...ostat is not set too cold Also check gasket condition Cabinet temperature is too high Thermostat set too high Set thermostat to lower temperature Poor air circulation in cabinet Re arrange product to allow proper air circulation Exterior thermometer is out of calibration Re calibrate thermometer Excessive amount of warm product placed in cabinet Allow adequate time for product to cool down Prolong...

Page 18: ...18 Part Number 9294045C 03 22 Troubleshooting Section 5 406P and 4048P Wiring Diagram ...

Page 19: ...Part Number 9294045C 03 22 19 Section 5 Troubleshooting 407P Wiring Diagram ...

Page 20: ...DELFIELD 980 SOUTH ISABELLA ROAD MOUNT PLEASANT MI 48858 800 733 8821 WWW DELFIELD COM 2019 Welbilt Inc except where explicitly stated otherwise All rights reserved Part Number 9294045C 03 22 ...

Reviews: