94
WATER SYSTEM CHECKLIST
A water-related problem often causes the same symptoms
as a refrigeration system component malfunction.
Example: A water dump valve leaking during the freeze
cycle, a system low on charge, and a starving TXV have
similar symptoms.
Water system problems must be identified and eliminated
prior to replacing refrigeration components.
Water area (evaporator) is dirty
• Descale as needed
Water inlet pressure not between 20 and 80 psig (1–5 bar,
138–552 kPa)
• Install a water regulator valve or increase the water
pressure
Incoming water temperature is not between 40°F (3°C)
and 90°F (32°C)
• If too hot, check the hot water line check valves in
other store equipment
Water filtration is plugged (if used)
• Install a new water filter
Vent tube is not installed on water outlet drain
• See Installation Instructions
Hoses, fittings, etc., are leaking water
• Repair/replace as needed
Water valve is stuck open, closed or is leaking
• Descale/replace as needed
Water is spraying out of the sump trough area
• Stop the water spray
Uneven water flow across the evaporator
• Descale the ice machine
Water is freezing behind the evaporator
• Correct the water flow
Plastic extrusions and gaskets are not secured to the
evaporator
• Remount/replace as need.
Summary of Contents for Manitowoc NEO UDP0080A
Page 2: ......
Page 18: ...18 Part Number STH098 06 19 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 74: ...74 Part Number STH098 06 19 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 166: ...166 Part Number STH098 06 19 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 176: ...176 Part Number STH098 06 19 ELECTRONIC CONTROL BOARD UDP0080 1 2 3 4 5 6 7 8 9 10...
Page 179: ......