USING YOUR GENERATOR
ECO-MODE SWITCH
This generator is equipped with an Eco-Mode Idle Control Switch
(Fig. 22). Engaging this switch allows the system to regulate the
engine speed and automatically adjust its fuel consumption to
match the required load. When the electrical load changes, the
generator engine will automatically speed up and slow down as
needed. This reduces fuel consumption and noise levels, while
extending runtime and engine’s lifespan.
Keep this switch engaged ONLY when the power load requirement is less than 2625W. Do not engage the Eco-Mode
Switch when the total load is more than 2625W. The generator engine must run at full speed to supply power for
anything over 2625W.
PARALLEL OPERATION
The parallel connection ports (Fig. 23) allow you to connect two
WEN generators to increase the total available electrical power.
The WEN Parallel Connection Kit can be purchased from
wenproducts.com.
Follow the instructions included with your
parallel connection kit for proper installation and operation.
IN CASE OF OVERLOAD
If your generator becomes overloaded from too much drawn
wattage, the overload indicator (red) on the control panel will
light up. Follow the instructions below when an overload occurs:
• When you’re close to overloading the generator, the overload
light will start to flash. Reduce the load by turning off and dis-
connecting your electronic device(s) until the overload light turns
off. Then you may continue to operate your generator.
• When you’ve overloaded the generator, the overload light will stay on and the reset button (Fig. 24) will activate
to cut off the output in 3 to 16 seconds, depending on the load. Reduce the load by turning off and disconnecting
your electrical device(s) until the overload light turns off. Wait about five minutes and then press the activated reset
button to reset the circuit. If no power is produced after resetting, turn off and disconnect all electrical devices and
restart your generator.
Fig. 22
Fig. 23
Fig. 24
ON
OFF
ECO-MODE
LIGHT
MEANING
RESOLUTION
GREEN (POWER INDICATOR)
RED (OVERLOAD)
ON
OFF
Generator output is normal.
No action needed.
ON
Flashing Continuously
Generator is exceeding rated output.
Reduce load on generator.
OFF
Flashes 1x
Repeating every 3 seconds
Voltage at alternator is too low.
No electrical output.
Check for loose connections.
Call
1-800-232-1195
for assistance.
OFF
Flashes 2x
Repeating every 3 seconds
Engine speed is too low.
No electrical output.
Check carburator and stepper motor.
Ensure Eco-Mode is OFF. Have genera-
tor serviced; call
1-800-232-1195
for
assistance.
OFF
Flashes 3x
Repeating every 3 seconds
Inverter temperature is too high. No
electrical output.
Turn generator off and let cool down fully
(1-2 hours) before restarting.
OFF
Flashes 5x
Repeating every 3 seconds
Voltage at alternator is too high.
No electrical output.
Have generator serviced; call
1-800-232-1195
for assistance.
OFF
Flashes 6x
Repeating every 3 seconds
Generator has exceeded rated output
and cut off power to protect itself. No
electrical output.
Turn OFF and disconnect loads. Press
RESET button on panel.Reduce load on
generator.
27